KYORITSU 8113 User Manual

Page 10

Advertising
background image

― 8 ―

― 8 ―

(2) Refer to Table 1 for output voltage against input. Set the

multimeter to the appropriate range. When using a digital
multimeter(3-1/2 digit), select the 200mV DC or 2V DC range.

Table 1

Note :

Measurements can be made up to 5A at the 2A range
position and up to 50A at the 20A range position.

(3) Before making measurements,adjust“DC A 0 Adj. control

knob”to zero output. For accurate measurements, it is a
recommended practice to make this zero adjustment for
every measurement. It is also necessary to make the zero
adjustment after every range changing as it may cause the
instrument to be off zero.

(4) Press the trigger to open the transformer jaws and clamp onto

one conductor only. Since the current measured will be displayed
as voltage, read it in amperes according to each range. For example,
take the reading as follows using a 3-2/1 digit digital multimeter.

Table 2

Note :

The display may slightly flicker on the 2A range because
of high sensitivity when the 200mV range is used.

Range Switch

Position

2A DC

20A DC

200A DC

Output Voltage

0−500.0mV(100mV/A) against 0−5A DC input
0−500.0mV(10mV/A) against 0−50A DC input
0−200.0mV(1mV/A) against 0−200A DC input

Range Switch

Position

2A

20A

200A

Digital Tester Readings

200mV Range

50.0mV

100.0mV

50.0mV

100.0mV

50.0mV

100.0mV

2V Range

0.050V
0.100V
0.500V
0.050V
0.100V
0.500V
0.050V
0.100V

0.50A
1.00A
5.00A

5.0A

10.0A
50.0A

50A

100A

Currents