Tork, Dzs400a, Specifications – NSi Industries DZS400A User Manual

Page 2: Specification writer’s guide, Ordering information, Wiring diagrams

Advertising
background image

TORK

1 Grove St., Mt. Vernon, NY 10550 • Tel: 914-664-3542 • Fax: 914-664-5052 • Internet: http://www.tork.com

MEMORY MODULE (MM) can be programmed at
any one location and inserted into another
DZS400A (with Memory Module socket) in any
other remote location.

OPTIONAL MEMORY MODULE PROGRAMMER – MMP

SPECIFICATIONS

Power Consumption: 6 VA Max.
Contact Ratings:

Type

Voltage

Rating

General

24-277 VAC, 30 VDC

10A

Purpose

Tungsten

120 VAC

360 watts

Pilot Duty

120-277 VAC

360 VA

Motor Load

120 VAC

1/4 HP

208-240 VAC

1/3 HP

Operating Temperature: -40° to +158°F (-40° to +70°C)

Enclosure:
Noryl

®

indoor/outdoor (NEMA 3R) is standard.

For metal indoor (add suffix Y to catalog #).
Other Mountings:
Metal indoor/outdoor (suffix O) - Model 9000A.
Flush with lock and key (suffix FLG) – Model 9011.
Bracket for panel mounting – consult factory.

SPECIFICATION WRITER’S GUIDE

1. Furnish and install where noted a 4 channel digital time switch with

portable memory module on front panel.

2. Memory module shall be capable of being programmed at any one

location and inserted into the new DZS400A (with memory module
socket) in any other remote location.

3. Optional programmer shall be available, Model MMP, capable of

accomplishing Windows based settings on a PC for easy duplication of
memory modules or individualized programs for multiple locations.

4. Controller shall program in AM/PM format.
5. Controller shall program in one minute resolution.
6. Display shall be of LCD type.
7. Controller shall be capable of 99 set points; separate scheduling for

each day of the week.

8. Controller shall have 365 day holiday capabilities with 24 single dates

and 4 seasons of unlimited duration.

9. Different daily schedules shall be programmable within each season.

10. Controller shall have Daylight Saving or Standard time.
11. Controller shall have automatic Leap Year correction.
12. Schedules shall be retained for 40 years without power.
13. Controller shall have 30 day backup for real time using field replaceable

9V lithium battery.

14. Controller shall be capable of manual override ON or OFF to the next

scheduled event using 1 button for each channel.

15. Unit shall have NEMA Type 3 indoor/outdoor enclosure as standard.
16. Controller shall be capable of having 2 different pulse durations 1-99

seconds, user settable and assignable to each channel.

17. Controller shall be capable of having astronomic on one (or all) chan-

nels with 1-99 minutes, plus or minus offset from Sunrise or Sunset.

18. To order specify TORK Model DZS400A.

Clock Input - VAC

Dry Contacts

Model

50/60 Hz

(unpowered)

DZS400A

120 / (208 - 240) / 277*

SPDT

ORDERING INFORMATION

Meets California

Energy Commission

Title 24 requirements.

PORTABLE MEMORY MODULE ON FRONT PANEL FOR EASY

INSERTION AND REMOVAL

* For 12VDC or 24VAC, consult factory.

For 208-240V,
connect one of
the line wires to
terminal N. Do
N O T bring any
neutral wire to
this terminal.

DZS400A

MULTI-PURPOSE, 4 CHANNEL WITH
PORTABLE MEMORY MODULE

365 Day Advance Single Holiday
and Seasonal Scheduling
Astronomic Option

WIRING DIAGRAMS

Windows based personal computer software & hardware
package makes programming the Memory Module as easy
as 1, 2, 3 by clicking on the mouse. The program can be
individualized or copied onto multiple memory modules for
use in different locations.

OPERATIONAL FEATURES

ON and OFF Set Points - 99 total per week

Astronomic -
1. Adjustable 10° - 60° Northern or Southern latitudes.
2. Each channel can be individually offset ±1-99 minutes
from both sunset and sunrise times.

Holidays - 1 to 24 individual dates

Seasons - 1 to 4 with different daily schedules which can
wrap around into the new year

Daylight Saving - Automatic adjustment (can be omitted)

Leap Year - Automatic compensation

Display - LCD

Manual Override - Until the next regularly scheduled ON or
OFF. Automatic operation then resumes.

Signal/Pulse Duration - 2 different settings per channel -

each 1-99 seconds.

Clock Format - AM/PM

Power Outage Backup - Permanent schedule retention for
upto 40 years. Snap-in lithium battery maintains real time.

Advertising