NSi Industries LC200 User Manual

Tork, Model lc200

Advertising
background image

TORK

MODEL LC200

Dual Stage Lighting Controller

DESCRIPTION,

INSTALLATION & OPERATION

Description:

The Model LC200 consists of an electronic
control and an electronic light sensor interact-
ing. The unit offers separate control of two
lighting zones, each with user settable on/off
light level setpoints. The Electronic control
also offers two digital inputs which will accept
a contact closure from any TORK Timer(s),
or existing EMS system to provide for inde-
pendent time-of-day override if required.

Features:

Single electronic light sensor with swivel
(Model EPC-1) which can be mounted up
to 1000 feet from controller

Dual outputs with independent adjustment
from 2 to 100 footcandles

Two independent “Time-of-Day” inputs

30 second delay on start-up

Power-On status indicator

Load status indication for each load

Installation:
1. Remove the Control from its enclosure,

push tab to right and swing unit to left and
remove.

2. Mount the enclosure at eye level using

screws or other suitable fastening device.

TORK

1 GROVE ST., MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

MLI-119(B)

®

NOTE: Disconnect all external power
before wiring to prevent electrical shock
or damage to equipment.
Wiring must com-
ply with appropriate codes.

3. KO’s top, bottom and side (1/2” and 3/4”)

a. Use bottom or side KO’s for Input

power, and load wiring. See wiring dia-
gram for connection.

*b. Use top KO’s for light sensor and

Time-of-Day control input wiring (rec-
ommended wire size is 18 to 22 AWG
twisted pair). See wiring diagram for
connection.

4. The electronic light sensor Model EPC-1,

can be mounted up to 1000 ft. away
through a standard 1/2” SPT connection
to an outdoor weatherproof junction box.
Use suitable tape or sealant on nipple
threads.

Must be mounted in the

upright position. See wiring diagram for
connection.

Setting The Light Level Adjustment:

NOTE: Setting the light level dials for both
Stage 1 and Stage 2 must be done when
ambient light levels fall to the actual point
when electrical lighting is required.

1. Move SET/RUN switch to the SET position.

2. Rotate Stage 1 and 2 light level dial clock-

wise to their maximum light level setting
(position 10)

3. Wait until the ambient light falls to the

point when Stage 1 electrical lighting is
required. Rotate the Stage 1 light level dial
counterclockwise until the lighting comes on.

4. Repeat step #3 above for Stage 2 electri-

cal lighting.

5. Return the SET/RUN switch to the RUN

position. The unit is now ready for operation.