Tork, Wiring diagrams, Electrical ratings – NSi Industries LC200 User Manual

Page 3: Contact ratings: sensor, Indicators, Time delay, Set point range, Time-of-day inputs, Temperature range, Standard epc-1 electronic photocell

Advertising
background image

ELECTRICAL RATINGS:

Voltage Input: 120/240/277 VAC 50/60 Hz

Power Consumption: 5VA Max.

Switching: SPDT (each stage)

CONTACT RATINGS:

Sensor:

Standard EPC-1 Electronic Photocell

Indicators:

LED
GREEN for Power
RED for CH1 & CH2 relay status

Time Delay:

30 Sec. ± 10 Sec.

Set Point Range:

2fc to 100fc

Time-of-Day Inputs:

The two relays can be remotely overridden by
attaching a closed dry-contact switch between
the “C” and the appropriate “TOD” contact.

Temperature Range:

– 40°F to 140°F
– 40°C to +60°C

VOLTAGES

NO

NC

Ballast

120 VAC

20A

10A

240/277 VAC

6A

3A

Tungsten

120/240/277

5A

3A

VAC

Resistive

120/240 VAC

20A

10A

277 VAC

12A

Pilot Duty

120/240 VAC

470VA

275VA

277 VAC

690VA

TORK

1 GROVE ST., MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

®

WIRING DIAGRAMS

LOAD 1

For 120 VAC

Operation

WHITE

BLACK

POWER

STAGE 1

STAGE 2

RUN

SET

STAGE 1

STAGE 2

LIGHT LEVEL

TOD1

TOD2

C

TOD1

TOD2

C

EPC

1

10

2

9

3

8

4

7

5

6

1

10

2

9

3

8

4

7

5

6

LOAD 2

EPC1

N
H

NC

LOAD 1

For 240 VAC

Operation

RED

BLACK

H
H

LOAD 2

LOAD 1

For 277 VAC

Operation

WHITE

ORANGE

N
H

LOAD 2

277V

120V 240V

NEUT

C

NC

NO

C

NC

NO

OUTPUT 2

LINE INPUT

OUTPUT 1

277V

120V 240V

NEUT

C

NC

NO

C

NC

NO

OUTPUT 2

LINE INPUT

OUTPUT 1

277V

120V 240V

NEUT

C

NC

NO

C

NC

NO

OUTPUT 2

LINE INPUT

OUTPUT 1

Do not apply any external
voltage to terminals TOD1,
C, TOD2, or EPC . For time
of day operation, connect
dry contact closure.
*See note 3b.

{