SELECTOR SWITCH:

If delayed response of 30 seconds is required (activa-
tion of photocell operation), move selector switch
labeled (DELAY, QUICK, SW) to the Left position
marked (DELAY).

If instance response is required move selector switch
to the center position marked (QUICK).

POTENTIOMETER:

Adjust potentiometer labeled (MIN MAX) for desired
light level actuation. If adjusted to the extreme left
(MIN position), turn ON will be 1 to 2 footcandles. If
adjusted to the extreme right (MAX position), turn ON
will be approximately 100 footcandles.

IMPORTANT: The potentiometer allows you to adjust
a turn ON ranging from 1 to 100 footcandles. OFF will
be 3 times the ratio of the ON foot candle level (see
example “B” below).

When using photocell input, the following can be
accomplished:

A. Photocell ON/Time OFF

B. Photocell ON/ Time OFF/ Time ON/ Photocell OFF.

DRY CONTACT INPUT

When connecting dry contact closure (i.e. remote
maintained SPST switch) to universal input termi-
nal labeled (1 2 3), connect wires to terminals 2
and 3. DO NOT USE TERMINAL 1. See illustration
on inside label.

2

SELECT SW

FUNCTION

DELAY QUICK SW

LIGHT LEVEL ADJ.

MIN

MAX

TORK

DGU100/DGUM100

7 DAY DIGITAL TIME SWITCH

INSTALLATION AND OPERATING

INSTRUCTIONS

READ INSTRUCTIONS CAREFULLY BEFORE SETTING UNIT

INSTALLATION

UNIT IS TO BE INSTALLED BY A LICENSED ELECTRICIAN

1. To remove unit from enclosure: Push tab on right to

swing unit to the left and remove.

2. Mount the enclosure at eye level using screws or

other suitable fastening device. Bring supply and
load wires in through the bottom or side knockouts.
DO NOT USE TOP.

Clock input wires to controller must be from a ded-
icated source i.e. no other loads connected to the
same circuit.

3. Install standard 9 volt lithium or alkaline battery

(not supplied) by gently squeezing the right side of
the battery cover on the front of unit and pull to
open. Pull out the battery connector and connect
the battery. Reinstall battery cover. Lithium should
be replaced every 3-5 years; alkaline every year.

NOTE: Unit can be fully programmed using battery
power only

4. Reinstall unit by reversing step #1 above and con-

nect wires to unit as per suggested wiring dia-
grams. See illustration on enclosure label.

Do not wire the photocell or remote maintained
switch while AC current is applied to the unit.

Do not apply any voltage from external source
to universal input terminals.

PHOTOCELL INPUT

When connecting Photocell (EPC1 ) to Universal Input
terminal labeled (1 2 3), connect wires to terminals 1
and 2. DO NOT USE TERMINAL MARKED 3. See
illustration on enclosure label.