tion of the unit to under 1 minute, allowing a check
of the wiring and the functions.

Step 4:

Set the extended time delay for the main load to
the appropriate time by adjusting switch #1, 2, and
3. See table for desired timing.

Step 5:

Set the warning period for 1 or 5 minutes using
switch # 4. See table for desired timing.

Step 6:

Remote ON/OFF momentary push buttons can be
connected at the remote input terminal between C
& ON to activate extended time, and C & OFF to
disable extended time.

SWITCH CONFIGURATION

OFF

OFF

ON

ON

OFF

OFF

ON

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

TIME

SET

1

2

3

*

*

*

*

*

*

*

ON

4

1/2 HR

1 HR

1-1/2 HR

2 HR

6 HR

9 HR

12 HR

TEST

OFF

OFF

OFF

OFF

ON

ON

ON

ON

*Switch 4 (ON) – 5 Minute Warning Period

*Switch 4 (OFF) – 1 Minute Warning Period

TORK

®

MLI-137(A)

1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

WIRING DIAGRAMS

Important Note:
When the Lighting Delay Switch is first activated –

A. If the time switch is set to ON, the lighting will

remain ON.

B. If the time switch is set to OFF, the lighting will

turn ON for 10 minutes. At the end of the 10
minute period, the warning blink will occur. The
lighting will remain ON for the 1 or 5 minute
warning period. If an extension of time is
required, press the remote ON button momen-
tarily, the lighting will remain on for an additional
1/2 - 12 hour extension of time.

OFF

ON

NO

C

NC

REMOTE
INPUT

TIME SWITCH

INPUT

MAIN LOAD OUTPUT

TERMINALS

INPUT POWER

MOMENTARY
PUSH-BUTTON SWITCH

LOAD

H

N

N

120

208
240

277

VAC

NC NO C

H

N

H

N

TORK TIME SWITCH

OUTPUT TERMINALS

C ON OFF

DO NOT APPLY

VOLTAGE

CAUTION: Turn power off at main circuit prior
to installation or when servicing this unit.