Tork, Digital time switch, Review/modify – NSi Industries EW103A User Manual

Page 2: Override - temporary, Override - long term, Specifications, Wiring diagrams, Warning

Advertising
background image

TORK

DIGITAL TIME SWITCH

TO SET CLOCK

Press MODE key until display shows CLK.
Press DAY key to select current day. Press HOUR key to select current
hour. Check A (AM) or P (PM). Press MIN key to select current minute.
Press ENTER key and the clock is set for current time and day.

TO SET SCHEDULE

For convenience, write out your desired schedule on a separate paper.

If display does not show SCH, press mode key until display shows SCH.

The display will Indicate it is ready to receive SCH setpoint #1.

Press DAY key to set day(s).

Note: The following is a listing of the sets of days which can be set:

1. M, T, W, TH, F
2. S, SU (Saturday and Sunday only)
3. M, T, W, TH, F, S, SU
4. Individual days: M or T or W or TH or F or S or SU

Press HOUR and MIN keys (check for AM or PM). Press ON/OFF key for
appropriate event.

Press ENTER key to store the information and display will indicate it is
ready to receive SCH setpoint #2.

Proceed for up to 14 setpoints. Then press MODE key and unit will
go to the AUTO (run) mode.

In the AUTO mode, the unit will display current time and day as well as load
status (ON and OFF).

Note: When the unit is returned to the auto mode, check the load status of the current
setting. If it is showing OFF but should be ON, press the override key. The unit will
correct itself at the next scheduled event and no further alteration will be necessary.

REVIEW/MODIFY

1. CLOCK - ALTER TIME

Press mode key until display shows CLK.

Press DAY, HOUR, and MIN keys to change to the correct time. Press
ENTER.

2. SCHEDULE - REVIEW

Press mode key until display shows SCH.

Press ENTER key repeatedly to review all the scheduled entries.

3. SCHEDULE - MODIFY

During the review (see previous section) any setpoint can be modified or
deleted. Use the HOUR, MIN and DAY keys to modify. Use the DELETE key
to eliminate that event. Press ENTER key after each modification.

OVERRIDE - TEMPORARY

In order to temporarily change the current ON or OFF status of a load, sim-
ply press the override key when the unit is in the AUTO mode. The altered
load status will flash. Override is in effect until the next scheduled event. In
order to cancel the override, press override key again.

OVERRIDE - LONG TERM

Press mode key until display shows MAN (manual). Normal schedule will
not be executed and the load status will remain unchanged as indicat-
ed. Press the OVERRIDE key to obtain the correct status or to alter
the load status.

®

UL

469D

LISTED

®

LR21743

MLI-163(B)

1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

EW101A EW120A EW103A

SPECIAL ENCLOSURE: -C -Y -FLG -O

3

SPST

4

LOAD

120/277VAC

E101A

E120A

1

2

N

L

N

TIMER

SUPPLY

TIMER

SUPPLY

120/277VAC

3

4

5

SPDT

1

2

L

N

LOAD

LOAD

N

N

E103A

3

DPST

4

LOAD

208 OR 240VAC

1

2

L1

L2

TIMER

SUPPLY

6

5

DPST

TIMER

SUPPLY

3

5

6

120/277VAC

SINGLE PHASE

4

L1

L1

L1

N

1

2

LOAD

N

LOAD

N

SPECIFICATIONS

Input Voltage: 120/208 - 277VAC, 50/60Hz. (Jumper selectable), 4VA max.
User Selectable by Jumper Setting:

See caution on front page regarding

clock voltage selection and circle your input voltage below.

120V 208-277V

Dry Contact Ratings:

WIRING DIAGRAMS

SERIES E101A (SPST) AND E103A (DPST)

SERIES E120A (SPDT)

TYPE

208-277

208-277

120VAC

208-277VAC

OF LOAD

120VAC

VAC

120VAC

VAC

N.O.

N.C.

N.O.

N.C.

Resistive

40A

40A

30A

30A

30A

30A

30A

30A

Inductive

40A

40A

30A

30A

30A

30A

30A

30A

Ballast

30A

20A

30A

20A

30A

10A

20A

10A

Tungsten

10A

10A

10A

2A

Pilot Duty

720VA

720VA

720VA

720VA

720VA 720VA

720VA

720VA

Motor

1 HP @ 120V; 1-1/2 HP @ 208V; 2 HP @ 240-277V

30A resistive @ 28 VDC

NO/NC 30A resistive @ 28 VDC

UL

CSA

UL and CSA

WARNING

!

Lockout power at main panel before initial wiring or servicing
of this time switch and any equipment connected to it. More
than one disconnect point may be required. Install and use in
accordance with national and local electrical codes. Use cop-
per wire AWG #8-16 suitable for 75°C (167°F). Metal enclo-
sure must be properly grounded.

Insulator must be
replaced below before
turning on electricity.
Inform electrician if it
is missing.

EW SERIES INSTRUCTIONS2003 11/18/03 5:02 PM Page 1

Advertising
This manual is related to the following products: