NSi Industries 1102 User Manual

Tork

Advertising
background image

TORK MODEL 1102

24 HR. TIME SWITCH

SWITCH: SPST

CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE

120-277VAC SINGLE PHASE

40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC

TIMING MOTOR: 208-277VAC 60Hz

POWER CONSUMPTION:
3 WATTS MAX.

INSTALLATION AND OPERATING INSTRUCTIONS

TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn
OFF. Place tripper on dial edge as shown in
figure and set point of each tripper to desired
operating time. CAUTION: Note if selected
time is AM or PM. Hold tripper against dial
edge and firmly tighten knurled screw.

Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)

TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicat-
ed by arrow on nameplate.

FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn
ON. Press down lever on left of nameplate to turn OFF.

TO REMOVE MECHANISM FROM CASE: Press lever near case latch to
release mainplate and swing the movement out. To replace, insert mainplate pro-
jections in slots opposite latch and swing movement in until it latches.

FOR 120 VAC

LOAD

H

Removable

Bridge

N

M

L

1

X

2

For separate motor terminals,

remove bridge from terminals L & 1.

O
F
F

O
N

TORK

Dial Calibrations

Knurled Screw

OFF TIME

(Dark Tripper)

ON TIME

(Light Tripper)

MANUAL

ON

LEVER

MANUAL

OFF

LEVER

TIME

TORK

®

1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

LI-562(A)

FOR 277 VAC

Advertising