TORK MODEL 7220

24 HR. TIME SWITCH

WITH SKIP-A-DAY

SWITCH: DPDT
CONTACT RATINGS:

40 AMP 120-277VAC
20 AMP INDUCTIVE

120-277VAC SINGLE PHASE

40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC

TIMING MOTOR:
120VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.

INSTALLATION AND OPERATING INSTRUCTIONS

TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.

TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.

FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.

TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.

TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).

TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release
mainplate and swing the movement out. To replace, insert main-plate projections in slots opposite
latch and swing movement in until it latches.

Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)

O
F
F

O
N

TORK

Dial Calibrations

Knurled Screw

OFF TIME

(Dark Tripper)

ON TIME

(Light Tripper)

MANUAL

ON

LEVER

MANUAL

OFF

LEVER

TIME

TORK

®

1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

LI-596(A)

RED

STUD

GREEN

ACTUATOR

M

1

X

2

L

3

4

5

LOADS

N

LOADS

TYPICAL FOR 120VAC SUPPLY

H

H

N

H

N

FRONT

REAR

L