Spectrex 20/20MI - Mini Triple IR (IR3) Flame Detector User Manual

Page 18

Advertising
background image

Spectrex Inc. - SharpEye

TM

Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011

10

Other fuels
The detector will react to other types of fires as follows:

Pan Fire Size: 1ft

2

(0.1m

2

)


Maximum Wind Speed: 6.5 ft/sec (2 m/sec)

Maximum Response Time: 10 sec

Table 3: Response Sensitivity Ranges

Type Of Fuel

% Of Max. Distance at

each Sensitivity Range

Gasoline 100%
N-Heptane 100%
Alcohol 95%

75%

JP4 75%
Kerosene 75%
Diesel Fuel

70%

Methane* 30%
Propane* 30%

* 0.5m plume fire

Table 4: Sensitivity to other fire sizes

Fuel

Fire Size Detection

Sensitivity

Distance

Maximum Detection Time
20/20MI-1

Jet Fuel

2 x 2 ft

40

132 ft (40m)

10 seconds

Jet Fuel

2 x 2 ft

20

65 ft (20m)

8 seconds

Advertising