Appendix B: Intrinsically Safe Connection For
20/20MI-XX-X-C


The 20/20MI-XX-X-C is intrinsically safe certified per ATEX Ex II 1GD, EEx ia IIC
T4. This model does not include the relay outputs.

In order to comply with the intrinsic safety requirements, barriers/ galvanic
isolators must be incorporated. This section will recommend types of barriers and
connection. To comply with Intrinsic safety requirements, any barriers/isolators
that will comply with parameters of the detector certification or lower and allow
proper operation of the detector will be acceptable.

The attached list is for example only.

a.

For power line

- MTL 5021, MTL5022, P&F KFD2-SL2-EX 1.B

b.

For 4-20mA output - MTL 7787, P&F KFD2-CR-Ex 1.30-300

c.

For RS-485 line

- MTL 7766AC



The Flame Detector limitation parameters, per input/output, are as follows:

Pin

Ref

Ui

Ii

Pi

Ci

Li

1 Vin
2 GND

30V 200mA 1W

0

0

3 4-20

mA

IN

4 4-20

mA

OUT

30V 200mA 0.5W

0

0

5 RS485A+
6 RS485B-

±12V 80mA 1W

0

0

7 Fault

relay

8 Fault

relay

rtn

30V X

X

0

0

9 Alarm

relay

10 Alarm

relay

rtn

30V X

X

0

0

11

Shield

0

0 0 0 0

12

EXT_BIT_SW 0

0 0 0 0

Advertising