Spectrex 20/20MI - Mini Triple IR (IR3) Flame Detector User Manual

Page 58

Advertising
background image

Spectrex Inc. - SharpEye

TM

Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011

50

Flame Response Sensitivity Test
All four samples of the Model 20/20MI-3 were exposed to the standard test
consisting of a 12 in. x 12 in. (0.3m x 0.3m) pan fire with fuels noted below. The
tests were conducted at FM Approvals in Norwood, MA, and the average results
for all four samples are as follows:

Distance to

Fire

Detector

Model

Fuel

Ft.

m

Sensitivity

setting

Response

(seconds -

average

20/20 MI-3

n-heptance

33

10

10

3.0

20/20 MI-3

n-heptance

24.7

7.5

7.5

4.2

20/20 MI-3

n-heptance

16.5

5

5

4.1

20/20 MI-3

n-heptance

8.2

2.5

2.5

8.2

20/20 MI-3

Diesel

23.1

7

10

3.8

20/20 MI-3

Diesel

17.3

5.3

7.5

5.5

20/20 MI-3

Diesel

11.5

3.5

5

6.4

20/20 MI-3

Diesel

5.7

1.7

2.5

9.2

20/20 MI-3

Ethyl Alcohol

24.8

7.5

10

4.6

20/20 MI-3

Ethyl Alcohol

18.5

5.6

7.5

3.2

20/20 MI-3

Ethyl Alcohol

12.4

3.8

5

4.8

20/20 MI-3

Ethyl Alcohol

6.1

1.8

2.5

3.6

20/20 MI-3

Jet A

23.1

7

10

1.9

20/20 MI-3

Jet A

17.3

5.3

7.5

4.3

20/20 MI-3

Jet A

11.5

3.5

5

6.1

20/20 MI-3

8 in.(20cm) dia. Pan
polypropylene pellets.

8 2.4

10

1.9


Field of View Test
One sample of the Model 20/20 MI-1, which has an identical enclosure to the
20/20 MI-3 and is considered representative of the series, was exposed to the 12
in. x 12 in. (0.3 m. x 0.3 m.) N-heptane pan fire during which time the viewing
angle was varied +/-50º from the centerline along the horizontal and vertical axes.
The following results were obtained:

Angle (Approximate)

Distance

Average Response Time

On centerline

33 ft. (10m.)

3 sec.

+ 50º horizontal

16.5 ft. ( 3 m.)

8.7 sec.

- 50º horizontal

16.5 ft. ( 3 m.)

8.1 sec.

+ 50º vertical

16.5 ft. ( 3 m.)

8.8 sec.

- 50º vertical

16.5 ft. ( 3 m.)

12 sec.

Advertising