5.Technical Specifications

5.1 Electrical Specifications

A. Operating Voltage: 18-32 VDC
B. Power Consumption:

Max. 25mA in Stand-by

Max. 50mA in Alarm

C. Electric input protection: The input circuit is protected against voltage-

reversed polarity, voltage transients, surges and spikes according to
MIL-STD-1275A.

D. Electrical outputs

• Dry Contact Relays:

Table 13: Contact Ratings

Relay
Name

Type

Normal
position

Maximum Ratings

Alarm

SPST N.O.

2A at 30VDC or 0.5A at 250 VAC

Fault *

SPST N.C.

2A at 30VDC or 0.5A at 250 VAC

• The FAULT relay will normally be energized and the contact will be closed during

normal operation of the detector. The contact will be open at Fault condition or low
voltage.

• The relay outputs are not available in the intrinsically safe model 20/20MI-XX-X-C.

• 4-20mA Current Output:

The 4-20mA is isolated sink option.
The maximum permitted load resistor is 600Ohm.

STATE

Output

FAULT

0 + 0.5mA

BIT FAULT

2mA±10%

NORMAL

5mA±10%

WARNING 10mA±5%
ALARM

15mA±5%

• Communication Network:

The detector is equipped with an RS-485 communication link that can be
used in installations with computerized controllers. The communications
protocol is Modbus compatible.

This protocol is a standard and widely used.
It enables continuous communication between a single standard

Modbus controller (Master device) and a serial Network of up to 247
detectors.

It enables connection between different types of Spectrex detectors or

other Modbus devices to the same Network.