3.3 False Alarms Prevention

The detector will not provide an alarm or a warning signal as a reaction to the
radiation sources specified below.

Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20Hz.

Table 5: Immunity To False Alarm Sources

Radiation Source

Immunity

Distance ft(m)

Sunlight IAD
Indirect or reflected sunlight

IAD

Incandescent frosted glass light, 100 W

IAD

Incandescent clear glass light, rough service, 100 W

IAD

Fluorescent light with white enamel reflector, standard office or
shop, 40 W (or two 20 W)

IAD

Electric arc [12mm (15/32 in) gap at 4000 V alternating current,
60 Hz]

IAD

Arc welding [4 mm (5/32 in) rod; 240 A]

See Table 6, 7

Ambient light extremes (darkness to bright light with snow, water,
rain, desert glare and fog)

IAD

Bright colored clothing, including red and safety orange.

IAD

Electronic flash (180 watt-seconds minimum output)

IAD

Movie light, 625 W quartz DWY lamp (Sylvania S.G.-55 or
equivalent)

6.5 (2)

Flashlight (MX 991/U)

IAD

Radiation heater, 1500 W

IAD

Radiation heater, 1000 W with fan

IAD

Quartz lamp (1000 W)

10 (3)

Mercury vapor lamp

IAD

Grinding metal

IAD

Lit cigar

1 (0.3)

Lit cigarette

1 (0.3)

Match, wood, stick including flare up

10 (3)

Advertising