Digital input (option), External switch/relay contacts, External ttl-compatible logic signal – West Control Solutions N8080 (for 1xxx) User Manual

Page 37: Transistor outputs, Relay 1 output

Advertising
background image

A.3

DIGITAL INPUT (OPTION)

Type:

Voltage-free or TTL-compatible operation.

May be connected to:

External switch/relay contacts or

TTL-compatible logic signal.

Maximum Input delay

(open - closed or “1" - “0"

transition):

1 second

Minimum Input delay

(closed - open or “0" - “1"

transition):

1 second

External Switch/Relay Contacts

Maximum Contact

Resistance (Closure):

50

Minimum Contact

Resistance (Open):

5000

External TTL-Compatible Logic Signal

Maximum Voltage (TTL) for

“0”:

0.8V

Minimum Voltage (TTL) for

“0":

-0.6V

Minimum Voltage (TTL) for

“1":

2.0V

Maximum Voltage (TTL) for

“1":

24.0V

A.4

TRANSISTOR OUTPUTS

Type:

NPN open collector. Output tied to Alarm 1,

Output 2 tied to Alarm 2.

A.5

RELAY 1 OUTPUT

Contact Type:

Single pole double throw.

Rating:

5A resistive @ 120/240V AC

PM090-A

Volume II

A-3

59135

Advertising