Troubleshooting guide, Troubleshooting guide 11 – Badger Meter 1200 User Manual

Page 11

Advertising
background image

TROUBLESHOOTING GUIDE

Problem

Possible Cause

Remedy

Meter indicates higher than

actual flow rate

Cavitation

Debris on rotor support

Increase back pressure

Clean meter

Meter indicates lower than

actual flow rate

Debris on rotor
Worn bearing
Viscosity higher than calibrated

Clean meter and add filter
Replace meter
Change temperature; change fluid;

recalibrate meter

Erratic system indication,

meter alone works well

Ground loop in shielding

Ground shield one place only

Indicator shows flow when

shut off

Mechanical vibration causes rotor to oscillate

without turning

Isolate meter

No flow indication, full or

partial open position

Fluid shock, full flow into dry meter or impact

caused bearing separation

New bearing required Move to location

where meter is full of fluid on startup

Erratic indication at low flow,

good indication at high flow

Low instrument sensitivity 10 mV rms turbine

signal is being lowered by loading of electronics

or instrumentation can’t sense low level signals

Amplify signal

No flow indication

Faulty pickup

Replace pickup, recalibrate as necessary

System works perfect, except

indicates lower flow over

entire range

Bypass flow, leak

Eliminate bypass valves, leak Repair or

replace faulty solenoid valves

Meter indicating high flow,

upstream piping at meter

smaller than meter bore

Fluid jet impingement on rotor, critical in gas

Change piping

Opposite effects of above

Viscosity lower than calibrated

Change temperature, change fluid or

recalibrate meter

Mass flow indication wrong

Wrong fluid density, critical in gas

Check fluid, electronics

Erratic or wrong indication

of flow

Loose pickup

Tighten pickup

Does not repeat at low flows

Repeats at high flow

System resolution readability

Increase resolution, that is,

1 out of 100 = 1%

User Manual

Page 11

November 2013