INSTALLATION INSTRUCTIONS

Before installation, the flow meter should be checked internally for foreign material, and be sure that the impeller spins freely

Also, the flow lines should be purged of all debris
The flow meter must be installed with the flow indication arrow, cast on the meter body, pointing in the correct direction of

flow The preferred mounting orientation is to have the meter installed in horizontal piping with the register facing upward
The liquid to be measured must be free from any large particles that may obstruct the rotation of the impeller If particles are

present, a mesh strainer should be installed upstream before operation of the flow meter Some sand and small particles are

permissible A 30 × 30 mesh strainer is recommended (0 020 opening)
The preferred plumbing setup is one containing a bypass line that allows meter inspection and repair without interrupting

flow If a bypass line is not utilized, it is important that all control valves be located downstream of the flow meter (See

Figure 2

and

Figure 3

)

Open valves slOwly tO ensure that entrapped air dOes nOt cause meter tO rOtate at an excessive speed.

damage can be caused by striking an empty meter with a high velOcity flOw Of gas Or liquid.

This is true with any restriction in the flow line that may cause the liquid to flash If necessary, air eliminators should be

installed to ensure that the meter is not incorrectly measuring entrained air or gas Do not locate the flow meter close to a

pump, because sever pulsation may negatively effect accuracy and flow meter life

ISOLATION VALVE

ISOLATION VALVE

AND FLOW RATE

CONTROL VALVE

FLOW METER

BYPASS VALVE

Figure 2: Meter installation using a bypass line

CONTROL VALVE

FLOW METER

Figure 3: Meter installation without using a bypass line

900 Series Positive Displacement Water Flood Meters