Series 228PV Plastic Tee Type Impeller Flow Sensor
Intrinsically Safe Electrical Installation
The Series 200 Sensor is approved, as an entity, as intrinsically safe when installed in conformance with Badger Meter
installation drawings 06-480-001 or 06-480-002 (sample shown in "SAMPLE INSTALLATION DRAWINGS" on page 8) as
specified on the blue label identifying an intrinsically safe sensor.
Entity approval implies that only the sensor is approved as intrinsically safe. Unless power supplies, equipment, and
instruments connected to the sensor are each rated either explosion-proof or intrinsically safe, these devices cannot be
installed in a hazardous area. The referenced installation drawing shows such apparatus located in a non-hazardous location.
Proper interfacing between the hazardous and non-hazardous areas must be provided. It is of absolute importance that
this interface be constructed and that all wiring be performed by qualified contractors. To ensure the intrinsic safety of the
installation, the connection of the intrinsically safe sensor to instruments and or power supplies must take place using an
approved intrinsically safe barrier located in a non-hazardous area. These barriers, listed below, are readily available from
various suppliers.
Manufacturer
Barrier
Crouse-Hinds Spec 504
Cat No. SB19140M0715
Measurement Technology Ltd.
MTL 715+ 15 V
R Stahl Intrinspak
9001/01-158-150-101
DIMENSIONS
Series No. Complete
228PV15XX-XXX
228PV2XXX-XXXX
228PV3XXX-XXXX
228PV4XXX-XXXX
A5
B5
C2
D3
E5
5.0" (127 mm)
5.16" (131 mm)
2.38" (60 mm)
3.97" (101 mm)
5.0" (127 mm)
5.63" (143 mm)
5.64" (143 mm)
2.88" (73 mm)
4.20" (107 mm)
5.0" (127 mm)
6.50" (165 mm)
6.83" (173 mm)
4.23" (107 mm)
4.68" (119 mm)
5.0" (127 mm)
7.38" (187 mm)
6.83" (199 mm)
5.38" (137 mm)
5.10" (130 mm)
5.0" (127 mm)
E
D
B
A
C
No Fittings
E
D
B
A
C
BSP Fittings
E
D
B
A
C
Flanged
Figure 1: A = Overall Length; B = Overall Height; C = Diameter;
D = Center of Tube to Top Height; E = Minimum Clearance for Sensor Removal
Page 6