Installation & Operation Manual

CALIBRATION

Badger Meter Impeller sensors use unique K and offset numbers for calibration. These numbers are derived from calibration

runs using NIST traceable instruments. Using both a K and an Offset number provides higher accuracy than using a K factor

alone. The K and Offset numbers for each tee configuration are listed in the "Calibration Table" below.

Calibration Table Columns

The table below provides calibration and operation data for Badger Meter Plastic Tee Sensors 1-1/2" to 4".

Column 1

Sensor Model Number

Columns 2 and 3

The K value and Offset values to use in our frequency equation:

Freq= Gpm

K

- offset

This equation describes the frequency of the output signal of all Badger Meter flow sensors. By

substituting the appropriate K and Offset values from the table, the sensor’s output frequency can be

calculated for each pipe size. This information is required when calibrating an output board or when

using the raw sensor data as direct output to interface with a device that is not a Badger Meter product.

Column 4

This column indicates the suggested flow range of each tee sensor. Badger Meter sensors will operate

both above and below the indicated flow rates. However, good design practice dictates the use of this

range for best performance.
Sensors should be sized for flow rather than pipe size. To prevent disturbances to the flow profile

always connect the sensor tee to pipe nipples measuring at least 10 pipe diameters in length on the up

stream (supply) side and at least 5 pipe diameters in length on the downstream (delivery) side before

making the transition in pipe size. If a lesser flow rate is chosen, an insufficient span exists for the proper

operation of these circuits. This can result in excessive ripple and fluctuations in signal, which can

adversely affect system performance.

Calibration Table

Model for

K

Offset

Suggested Operating

Range (gpm)

228PV15xx-xxxx

228PV20xx-xxxx

228PV30xx-xxxx

228PV40xx-xxxx

1.697

2.8429

8.309

13.74283

-0.316

0.1435

0.227

0.23707

5…100

10…200

20…300

40…500

Page 7

January 2013