PROGRAMMING

MPORTANT

I

You must connect terminals 1 and 5 together to enable the programming mode. After all programming is complete, remove the

connection between terminals 1 and 5 to prevent the unit from being reprogrammed by mistake.

To access the programming screens, press

repeatedly until the Program Mode (1 through 7) you want displays on

the screen .
1 . Once you select a program, press

R

to either cause the left digit of that value to flash (scale factors modes 1, 4 & 6), or

to change the parameters for the other programming modes (Decimal Point Position and Totalizer Reset) .

2 . On program modes 1, 4 & 6, use

R

and

in combination to choose individual digits and change their value .

OTEE:

N

On program modes 1, 4 & 6, you can advance to the next program mode only if a digit is not flashing . Press

R

until the display stops flashing .

R

1.01.000

Mode 1E: Totalizer Scaler multiplies the input pulses by this number (programmable from 0 .0001

to 99 .9999) and displays the results as the totalizer value .

R

2. oFF

Mode 2E: Totalizer Decimal Point sets the decimal point on the totalizer display from no decimal

(OFF) to 0 .00000 .

R

3. 1.000

Mode 3E: Rate Scale Factor Decimal Point sets the decimal in Rate Scale Factor number, from no

decimal to 0 .000 .

R

4. 9999

Mode 4E: Rate Scale Factor multiplies the input pulses by this number, which can be programmed

in conjunction with the Rate Decimal Point for a number from 0 .001 to 9999 .

R

5. oFF

Mode 5E: Rate Decimal Point sets the decimal point on the Rate of Flow display from no decimal

(off) to 0 .0000 . You can program the display to have a dead zero (----0), for a 5-digit display with the

least significant digit always being 0 .

R

6.0.9999

Mode 6E: Pulse Output Scale Factor multiplies the input pulses by a number from 0 .0001 to 0 .9999

and sends them to output terminals 6 & 7 .

R

7. on

Mode 7E: Front Panel Reset Enable When set to ON, press

R

to reset the totalizer to zero . When

set to OFF, the totalizer can only be reset through the remote reset input

(see

“Wiring Instructions” on page 7

) .

R

8. on

Mode 8E: Pulse Output Enable When set to ON, the solid-state relay output will pulse to

re-transmit input pulses . If set to OFF, it will not activate . Use the OFF setting to conserve battery

life if not using the output .

User Manual

Page 9

March 2014

REG-UM-00836-EN-11