Dwyer VRLS User Manual

Dwyer instruments, inc, Model vrls vibrating rod level switch, Bulletin l-vrls

Advertising
background image

Model VRLS Vibrating Rod Level Switch

Specifications - Installation and Operating Instructions

Bulletin L-VRLS

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Service:
Dry powder or bulk materials compatible with wetted materials.
Sensitivity: Min. bulk density of 20 lb/ft

3

(320 kg/m

3

).

Wetted Materials: 304 SS.
Temperature Limits:

Ambient: -40 to 140°F (-40 to 60°C);
Process: -40 to 176°F (-40 to 80°C).

Pressure Limit: 150 psi (10 bar).
Power Requirement: 20 to 250 VAC/VDC, 50/60 Hz.
Power Consumption: 15 VA.
Enclosure: Aluminum, painted.
Enclosure Rating: IP65.
Switch Type: SPDT.
Electrical Rating: 5 A @ 250 VAC.
Electrical Connections: Screw terminals.
Conduit Connection: 1/2˝ female NPT x 2.
Process Connection: 1˝ male NPT.
Indication Lights: Internal: green and red LED.
Sensing Delay: 0 to 6 s.
Weight: 4.4 lb (2.0 kg).

The Model VRLS Vibrating Rod Level Switch is an economical choice in level
detection of powders and bulk solids. Ideal for silo or hopper applications, its probe
design allows for self-cleaning, ensuring no build-up of material and accurate
detection. Sensitivity is adjustable for detection ranging from large granular
material to small powders with low bulk densities.

Operating Principle
The vibrating probe level switch is a system kept in resonance by piezoelectric
elements. When the vibration of the probe is damped by the surrounding medium,
the change in resonant frequency is detected by an electronic unit and converted
into a digital switching signal. Sensitivity adjustment for different detected materials
is not frequent, as there is no additional circuitry for signal amplification.

Electrical Connections
Terminal Functions
• L+, N-: Power
• NC, COM, NO: Relay Output
• Ground Connection

Panel Functions
-PWR: Power
-SIGNAL: Output Signal
-FSH (Fail Safe High): After power is connected, signal indicator lamp will turn on
and the switch will close. When probe detects material, the signal indicator lamp
will turn off and the switch will open.
-FSL (Fail Safe Low): After power is connected, the signal indicator lamp will turn
off and the switch will remain open. When probe detects material, the signal
indicator lamp will turn on and the switch will close.

4-9/32

[108.83]

4-29/64

[113.03]

1˝ NPT

51/64

[20.19]

10-27/32˝

[275.35]

Ø3/4

[18.87]

Electrical Connections
Terminal Functions:
• L+, N- : Power
• NC, COM, NO: Relay Output
• Ground Connection

Advertising