Dwyer 40M User Manual

Dwyer instruments, inc, Series 40t/40m digital temperature switch

Advertising
background image

Programming Device with Configuration Key
The Model 40X-K is not battery powered and requires that the device being
programmed be powered. If a power source is not available, a 40X-PS
power supply must be installed into the port on the edge of the key.

Copying Parameters to Configuration Key
1. Cut off power to the temperature switch
2. Connect the key to the temperature switch
3. Turn on power to the temperature switch or connect the power supply

to the key (LED on key will be green and the temperature switch will flash
“CIn”)

4. Press and hold the SET button on the temperature switch for 4 seconds

(display will flash “St”)

5. Release the SET button on the temperature switch, the press and hold

the SET button again for 4 seconds. (“St” on display will stop flashing
and the LED on the key will turn red)

6. Do not disconnect the key while the LED is red, as it is copying the

parameters

7. After LED on key returns to green, it is okay to disconnect the key. (If

using 40X-PS power supply, disconnect the power supply before
disconnecting the key)

Copying Parameters to Temperature Switch
1. Cut off power to the temperature switch
2. Connect the key to the temperature switch
3. Turn on power to the temperature switch or connect the power supply

to the key (LED on key will be green and the temperature switch will
read “CIn”)

4. Press and hold the button on the configuration key
5. After one second release the button on the key. Parameters will be

copied from the key to the temperature switch. (LED will turn red)

6. The display on the temperature switch will read “PrG” and the LED will

turn green once the temperature switch has been programmed
successfully.

7. Do not disconnect the key while the LED is red, as it is copying the

parameters

8. After LED on key returns to green, it is ok to disconnect the key. (If using

40X-PS power supply, disconnect the power supply before disconnecting
the key)

MAINTENANCE, CLEANING AND REPAIR
After final installation of the unit no routine maintenance is required. Clean
the surface of the display controller with a soft and damp cloth. Never use
abrasive detergents, petrol, alcohol or solvents. A periodic check of the
system calibration is recommended. The Series 40T/40M is not field
serviceable and should be returned if repair is needed (field repair should
not be attempted and may void warranty). Be sure to include a brief
description of the problem plus any relevant application notes. Contact
customer service to receive a return goods authorization number before
shipping.

Out 1 solidly lit
Out 1 flashing

°C
°F
Loc
Pr1

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

©Copyright 2013 Dwyer Instruments, Inc.

Printed in U.S.A. 5/13

FR# R5-443741-00 Rev. 4

The Series 40T/40M Digital Temperature Switch accepts a variety of
inputs to allow temperature measurements and set points up to 1999°F
(1300°C). Observing the current status of the control is made easier with
the 3-1/2 digit, multi-color LED display that has alarm, defrost and output
symbols. For added versatility, the temperature units can be field selected
for °F or °C. For cooling applications, manual defrost mode can be initiated
by pushing a single button. A flashing alarm informs users when the current
temperature exceeds preset limits. When programming multiple units, a
programming key is available to reduce set up time.

INSTALLATION
Note: Unit must be mounted away from vibration, impacts, water and
corrosive gases.
• Cut hole in panel 71 x 29 mm (2.80 x 1.14 in)
• Apply silicone around the perimeter of the hole to prevent leakage
• Insert unit into hole from the front side of the panel
• Slide the mounting bracket securely against the panel from the rear of

the unit

• Wiring diagram is displayed on top of the control

ADJUSTING PARAMETER VALUES
In order to change the parameter values, follow the procedure below:
• Press UP ARROW and DOWN ARROW simultaneously for four seconds

until PA is displayed

• Press SET
• Use UP ARROW or DOWN ARROW to adjust value to -19
• Press SET
• Press UP ARROW and DOWN ARROW simultaneously for four seconds

until SP is displayed

• Use UP ARROW or DOWN ARROW to cycle through parameters
• Press SET to view value of parameter
• Use UP ARROW or DOWN ARROW to adjust value of parameter
• Press SET to store value
• Press UP ARROW and DOWN ARROW simultaneously for four seconds

to exit menu

Series 40T/40M Digital Temperature Switch

Specifications - Installation and Operating Instructions

Bulletin T-40T

SPECIFICATIONS
Range:
Current: -1999 to 1999;

Voltage: -1999 to 1999;
K T/C: -140 to 1999°F (-100 to 1300°C);
J T/C: -140 to 1450°F (-100 to 800°C);
RTD: -320 to 1200°F (-200 to 650°C);
PTC: -58 to 300°F (-50 to 150°C);
NTC: -40 to 230°F (-40 to 110°C);
N. RTD: -110 to 570°F (-80 to 300°C).

Input: RTD thermocouple, thermistor current and voltage (depending on
model).
Output: 16A @ 250 VAC SPDT relay (max current allowed is 10A).
Control Type: On/off.
Power Requirements: 12 to 24 VAC/VDC, 115 VAC or 230 VAC
(depending on model).
Accuracy: ±1% F.S.
Display: 3-1/2 digit red display.
Resolution: 0.1°C.
Memory Backup: Non-volatile memory.
Temperature Limits: 32 to 131°F (0 to 55°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: IP 65.
Agency Approvals: UL, CE.

DISPLAYING ROOM TEMPERATURE
If the P5 parameter is set to display the temperature set point, the probe
temperature can be displayed by pressing the DOWN ARROW key for two
seconds until Pb1 is displayed. Next, hit the SET key. To return to the
normal display, press SET key.

MANUAL DEFROST ACTIVATION/DEACTIVATION
To manually activate the defrost cycle, press the UP ARROW key for four
seconds. This feature is disabled during heating operation.

PARAMETER LOCK OUT ACTIVATION/DEACTIVATION
The key pad lock out can be activated/deactivated by pressing the SET
and DOWN ARROW keys simultaneously for two seconds. The display will
flash Loc or UnL to signify the change in states.

ALARM BUZZER RESET
The audible alarm can be silenced by pressing any key.

RESTORING FACTORY DEFAULT SETTINGS
Factory settings can be restored by following the below procedure:
• Pressing the UP ARROW and DOWN ARROW keys for four seconds

until PA is displayed

• Press the SET key
• Press the UP ARROW or DOWN ARROW to adjust the value to 743
• Press SET key
• Pressing the UP ARROW and DOWN ARROW keys for four seconds

until dEF is displayed

• Press SET key
• Press the UP ARROW or DOWN ARROW to adjust the value to 149
• Press SET key
• Cycle the power after the flashing dEF goes away

Output 1 is active
Either modification of set point or call for load during
load protection (C1 or C2)
Defrost cycle is active
Alarm condition is present
Temperature is measured in °C
Temperature is measured in °F
Key pad is locked
Probe 1 error

DISPLAY MESSAGES

2-31/64

[63.22]

1-3/32

[27.94]

3

[76.20]

1-11/32

[33.99]

2-3/8

[60.33]

3-3/16

[80.92]

2-3/16

[55.52]

7/16

[10.92]

Advertising
This manual is related to the following products:

40T