Series TS Digital Temperature Switch

Specifications - Installation and Operating Instructions

Bulletin E-90-TS

The TS Digital Temperature Switch is designed for many
heating and cooling applications. The probe temperature is
displayed on the bright 3-digit, red LED. The user is able to
program 12 different parameters including set point,
hysteresis, cycle time, and ambient probe adjustment using
the front keypad. The unit features error or alarm messaging
and password protection. Select between temperature
display in °F or °C, and 110 VAC, 230 VAC, or 12 VDC
power supplies. The TS includes a thermistor with 5 ft (1.5
m) cable, fitting clips for panel mounting, and instruction
manual.

INSTALLATION
NOTE:

Unit must be mounted away from vibration,
impacts, water and corrosive gases.

Cut hole in panel 2.80 x 1.14 inches (71 x 29 mm).

• Apply silicone (or rubber gasket) around the perimeter of

the hole to prevent leakage.

• Insert unit into hole in the panel.

• Slide removable fitting clips onto unit from the back until

secure to panel.

• Remove back cover to wire unit.

• Wiring diagram is displayed on the top of the unit.

(Note: PROBE CABLE LENGTH MUST NOT EXCEED
328 ft (100 m). DO NOT INSTALL PROBE CABLE NEAR
POWER CABLES).

• Replace cover once wiring is completed.

WIRING DIAGRAM

PARAMETERS

Description

Units

Range

SP Set Point

Degrees

r1 to r2

r0

Differential or Hysteresis

Degrees

1 to 20

r1

Lower Value Set Point

Degrees

-50 to 150°

r2

Higher Value Set Point

Degrees

-50 to 302°F (-50 to 150°C)

d0 Heating or Cooling Control Option

Ht/Co

d2 Time for Defrosting

Minutes

0 to 59 min.

d8 Interval Time between

Hours

1 to 24 hr.

Defrosting

c0 Min. Stop Time for Load

Minutes

0 to 59 min.

c1 Continuous Cycle Time

Hours

0 to 24 hr.

P1 Ambient Probe Adjustment

Degrees

-10 to 10

H5 Parameter Access Code

Numeric

0 to 99

(SET AT 00 FROM FACTORY)

t0

Max. Temp. on Display

Degrees

-50 to 302°F (-50 to 150°C)

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS

Probe Range: -58 to 302°F (-50 to 150°C).

Input: 1.5-inch (4 cm) thermistor (1000Ω @ 25°C) with 5-foot
(1.5 m) cable.

Accuracy: ±1°.

Resolution: ±1 digit.

Output: 16 amp SPDT relay @ 250 VAC.

Horsepower Rating (HP):

1

/

3

HP for 8 amp and

3

/

4

HP for

16 amp.

Supply Voltage: 110 VAC, 230 VAC or 12 VDC/VAC, 24
VDC/VAC (depending on model).

Supply Power: 4 VA (230 V).

Ambient Temp: 14 to 158°F (-10 to 70°C).

Storage Temperature: -4 to 176°F (-20 to 80°C).

Front Panel Protection: IP64.

Display: 3-Digit, Red or Green (depending on model).

2.95
[75]

1.34
[34]

2.72
[69]

1.10
[28]

1

2

7

8

9

10 11

SUPPLY

load

power

t