Monitor and control temperature in heating and cooling applications with the
Series TCS Thermocouple Switch. The Series TCS offers a wide temperature
range, two selectable alarm sets, and an internal buzzer indicating alarm condition
or error. The user can define set point, heating/cooling regulation, cycle time, alarm
configuration, load status, and ambient probe adjustment. The thermocouple
switch features password protection and error/alarm messaging. Temperature and
output status is indicated on the bright red LED display. Use the configuration key
(sold separately) to quickly program multiple units. The Series TCS includes a
fitting clip for panel mounting, gasket, rear terminal cover and instruction manual.

INSTALLATION

Note: Unit must be mounted away from vibration, impacts, water and corrosive
gases.

• Cut hole in panel 2.80 x 1.14 inches (71 x 29 mm).
• Apply silicone (or rubber gasket) around the perimeter of the hole to prevent

leakage.

• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until secure to panel.
• Remove back cover to wire unit.
• Wiring diagram is displayed on the top of the unit.
• (Note: PROBE CABLE LENGTH MUST NOT EXCEED 238 ft (100 m). DO NOT 

INSTALL PROBE CABLE NEAR POWER CABLES).

• Replace cover once wiring is complete.

Series TCS Thermocouple Switch

Specifications - Installation and Operating Instructions

Bulletin E-90-TCS

SPECIFICATIONS
Probe Range:
32 to 999°F (0 to 700°C) for Type J thermocouple; 32 to 999°F (0 to
999°C) for Type K or S thermocouples.
Input: Type J, K or S thermocouple.
Output: SPDT relay rated 16A @ 240 VAC resistive.
Horsepower Rating (HP): 1 HP.
Control Type: ON/OFF.
Power Requirements: 115 VAC, 230 VAC, 12 VAC/VDC or 24 VAC/VDC
(depending on model).
Accuracy: ±1% FS.
Display: 3-digit, red, 1/2˝ (12.7 mm) digits, plus sign.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Temperature Limits:

Ambient: 32 to 158°F (0 to 70°C);
Storage Temperature: -4 to 176°F (-20 to 80°C).

Weight: 2.3 oz (65 g).
Front Panel Rating: IP64.
Agency Approvals: CE, cUR, UR.

WIRING DIAGRAM

3

[76]

1-11/32

[34]

2-3/8

[60]

1-7/64

[28]

LOVE CONTROLS DIVISION

Phone: 219/879-8000 www.love-controls.com

DWYER INSTRUMENTS INC.

Fax: 219/872-9057 e-mail:[email protected]

P.O. BOX 338 - MICHIGAN CITY, INDIANA 46360, U.S.A.

1

2

+

Probe input

7

8

POWER

SUPPLY

9

10

11

NC COM NO

OUTPUT

Advertising