Dwyer PBLTX User Manual

Page 2

Advertising
background image

5. Wiring

An external power supply delivering 10-28 VDC with minimum

current capability of 40 mA DC (per transducer) is required to

power the control loop. See Fig. A for connection of the power

supply, transducer and receiver. The range of appropriate re-

ceiver load resistance (RL) for the DC power supply voltage avail-

able is expressed by the formula:

RL Max =Vps – 10V

20 mA DC

Shielded cable is recommended for control loop wiring.

Black wire is negative (-) and red wire is positive (+) in Fig. B.

MAINTENANCE

After final installation of the pressure transducer and its compan-

ion receiver, no routine maintenance is required. A periodic check

of system calibration is suggested. The Series PBLTX transduc-

ers are not field repairable and should be returned if repair is

needed (field repair should not be attempted and may void war-

ranty). Be sure to include a brief description of the problem plus

any relevant application notes. Contact customer service to re-

ceive a return goods authorization number before shipping.

CAUTION: Do not exceed specified supply

voltage ratings. Permanent damage not cov-

ered by warranty will result. This device is not

designed for 120 or 240 volt AC operation.

Use only on 10 to 28 VDC.

INSTALLATION

1. Location: Select a location where the temperature of the trans-

ducer will be between 0 and 176°F (-18 to 80°C). Distance from

the receiver is limited only by total loop resistance.

2. Position: The transducer is not position sensitive. However all

standard models are originally calibrated with the unit in a posi-

tion with the diaphragm downward. Although they can be used at

other angles, for best accuracy it is recommended that units be

installed in the position calibrated at the factory.

3. Mounting: The transducer can be mounted via several meth-

ods. It can be suspended from the electrical cable, it can be

placed resting on the bottom of the tank in either horizontal or

vertical orientation, or it can be attached to a pipe or hang wire by

the 1/2˝ NPT male connection on the top of the housing.

4. Wire Length: The maximum length of wire connecting the

transducer and receiver is a function of wire size and receiver re-

sistance. Wiring should not contribute more than 10% of the re-

ceiver resistance to total loop resistance. For extremely long runs

(over 1000 feet), choose receivers with higher resistance to min-

imize the size and cost of connecting leads. Where wiring length

is under 100 feet, wire as small as 22 AWG can be used.

POWER
SUPPLY
10-28 VDC

-

RECEIVER

BLACK

RED

PRESSURE

TRANSDUCER

mA

Fig. A

Fig. B

BLACK (-)

RED (+)

Advertising