Dwyer UTS User Manual

Page 10

Advertising
background image

Setting the Series UTC Relay Values
You can set the relays to five different configuration modes: Level, Distance and
Flow (where applicable), Volume and Totalization (the last two modes should be
configured only after Volume/Totalization options were enabled in the Chapter 5,
Additional Features). Use NEXT or BACK buttons to toggle between modes and
ENT to select the mode. After selecting an indication mode, move on to set the first
relay parameters.

Relays Setup Options
For example, if the Series UT is set to flow indication mode, the relay can be set to
flow/distance or level values. In any other unit or SW version, the relay
configuration is done for level or volume values.

Each of the five relays in the Series UT allows you to define open and close values
for the switch, enabling its use for functions such as triggering an alarm or
controlling pumps.

In addition, relay four (4) can be configured to report error messages and relay five
(5) for flow totalization pulse setup (see detailed configuration instructions on page
10).

The relay values function as follows:
Open value: (Default = 0) The relay opens if the level measured in the tank is

higher than the entered open value.

Close value: (Default = 0) The relay closes if the level measured in the tank is

lower than the entered close value.

To Set the Relay Values for Level or Distance:

Relay values can be configured in two separate screens when set to flow, volume
or totalization (after setting the Series UT was set to of these indications).

As shown in the above example, relay values were configured in the following way:
000001 was entered in the high numbers H=1, and 20,000 was entered in the low
numbers L=20,000, which mean a total value of 120,000 gallons.

Page 9

Indication

Mode
Relay
Mode

Non Flow

Application

Flow

Application

Dist. Level Vol.

Dist., Level Vol.

Flow

Total.

Flow, Dist.,

Level

Flow,
Total.

NOTES:
The indication mode default state is Level. The chosen mode will be applicable for
all five relays. The close value must be lower than the open value for each relay,
otherwise an message is displayed. An message is displayed if a
relay value is greater than the tank height value.

In case of no measurement (caused by electronic problem or acoustic
interference) relays will switch to Close state.

For safety reasons relays parameters will reset when the following parameters will
be modified: Tank height, relays indication mode (Level/ Distance/Flow),
measurement mode (except when changing from Level to Distance and vise
versa) Flume/Weir type, measurement units, strapping table.

Press/Action

to enter relay

setup.

to assign an

indication mode for
the relays.

to enter open

mode.

to enter values

for the relay.

Press at the end
of entering a value
for relay 1, to
enter close value
parameters.

Press on the far
right digit to save
the value.

Display

and

and

and

Explanation

With the RELAY icon flashing.

Choose the desired relay configuration
mode: Level, Distance, Flow,
Totalization
or Volume. Use the NEXT
button to toggle between indication
modes and ENT to select the mode.

Enters the open values mode of the
relay setup. The appropriate relay
number flashes throughout the process
of defining values for that relay.

Displays 0 or the previously entered
relay value.

Use to enter the relay value.

Enters close values mode of the relay
setup. Enter and save the close values
in the same way as described above for
the open values.

Repeat the previous steps to set an
open/close values for each relay to be
used. (If you do not want to set a value
for every relay, use the Esc button to
exit the relays set-up mode.)

or

or

NOTES:
In DISTANCE mode, the OPEN value entered for a relay should be greater than
the CLOSE value entered for the relay, otherwise an is displayed.
Relay OPEN and CLOSE values in DISTANCE mode should be different by a
resolution of more than 3 cm.

Press/Action

to enter relay

setup.

to assign an

indication mode.

Display

For example,

and

For example,

Explanation

With the RELAY icon flashing.

Choose FLOW from the optional modes,
and press ENT.

Select the relay number you wish to
configure, using NEXT and BACK
buttons and press ENT. Select OPEN
and press ENT.

This screen allows you to enter up to
four digits of high numbers of flow
values.

Use this screen to enter low numbers of
up to five digits of flow values.

Enter relay values for Close mode, as
described above for Open mode.

or