Dwyer CDW User Manual

Dwyer instruments, inc, Bulletin e-cdw

Advertising
background image

Series CDW Wall Mount Carbon Dioxide/Temperature Transmitter

Specifications - Installation and Operating Instructions

Bulletin E-CDW

The Series CDW Wall Mount Carbon Dioxide/Temperature
Transmitter
combines accurate CO

2

measurements with a

passive temperature output. The Non-Dispersive Infrared
(NDIR) sensor continuously updates the calibration through a
proprietary logic feature which limits the amount of error due to
drift. The CDW series is ideal for building automation systems
to help control the fresh air intake in a room.

INSTALLATION
Warning:
Disconnect power supply before installation to prevent
electrical shock and equipment damage.
Make sure all connections are in accordance with the job wiring
diagram and in accordance with national and local electrical
codes. Use copper conductors only.

Caution: Use electrostatic discharge precautions (e.g. use of
wrist straps) during installation and wiring to prevent equipment
damage.

Do not exceed the ratings of this device, permanent damage not
covered by warranty may result.

MOUNTING
1. Press the release button on the bottom of the unit in order to

remove the cover as shown in Figure A.

2. Use the appropriate mounting holes and screws to secure the

base unit to the mounting surface.

3. Slide the wires through the wiring slot and make proper wiring

connections per the wiring diagram in Figure B.

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Range:
0 to 2000 PPM CO

2

.

Accuracy: ±100 PPM @ 22C.
Temperature Dependence: 0.2% FS per C Stability < 2% of
FS mover life of sensor.
Non-linearity: < 1% of FS.
Pressure Dependence: 0.13% of reading per mm of Hg.
Response Time: 3 to 5 minutes for 90% step change.
Ambient Operating Temperature: 32 to 122°F (0 to 50°C).
Storage Temperature: -4 to 158°F (-20 to 70°C).
Power Requirements: 18 - 30 VAC RMS 50/60 Hz, 18 to 42
VDC polarity protected.
Power Consumption: 1.75 VA average 3.25 VA peak.
Sensor: Non-Dispersive Infrared Sensor.
Output: 0 to 10 VDC for CO

2

; 20K Ohm NTC Thermistor for

temperature.
Weight: 0.5 lb (227 g).
Agency Approval: CE.

3-7/32

[81.76]

1-5/64

[27.61]

1-1/4

[31.75]

1-9/32

[32.51]

1/4

[6.35]

19/32

[15.14]

3-35/64

[90.04]

3-31/32

[100.84]

4-5/8

[117.48]

CL

SENSOR

7 PIN

CONNECTOR

THERMISTOR

INTERFACE

CONNECTOR

MOUNTING

HOLES

MOUNTING

HOLES

SLOT FOR

WIRING

LED

Figure A

Advertising