Series DCP100A/200A Pressure Modules

Specifications – Installation & Operating Instructions

The DCP100A or DCP200A pressure mod-
ules are designed exclusively for use with
the Dwyer

®

DCT1000 Dust Collector Timer

Controller boards for on-demand cleaning
requirements. These series of modules are
available in 10

″ w.c. [2.49 kPa] or 20″ w.c.

[4.98 kPa] ranges, which allow for differential
process pressure measurement as indicat-
ed on the display of the master controller.
An isolated 4-20 mA readout channel is pro-
vided for remote pressure display. The 4-20
mA output may be wired either for use with
an external power supply and indicator or
using the isolated on-board 24 volt power
supply to power the loop.

Table of Contents Page No.
1.0

Installation . . . . . . . . . . . . . . . . .2

1.1

Location . . . . . . . . . . . . . . . . . . . .2

1.2

Connections . . . . . . . . . . . . . . . . .2

1.3 Pressure Module Installation . . .2-3
1.3.1 Alarm Mode Switch Connection . .3
1.3.2 Alarm Reset Switch Connection . .3
1.3.3 Connecting the 4-20 mA loop . . .3
1.3.4 Connecting the Alarm Relay . . . . .3

Bulletin E-97-M

SPECIFICATIONS
Pressure Ranges:
10˝ w.c. or 20˝ w.c.
Temperature Limits: -40 to 140°F
(-40 to 60°C).
Pressure Limit: 10 psi (68.95 kPa).
Pressure Limit (differential): 10 psi
(68.95 kPa).
Accuracy: ±1.5% F.S. @ 73°F (22.8°C).
Output Signal: 4-20 mA.
Alarm Contacts: 1.5A inductive load, 3A
resistive load @ 30 VAC or 40 VDC.
Process Connections: Two barbed con-
nections for use with 1/8˝ (3.18 mm) or
3/16˝ (4.76 mm) I.D. tubing.
Weight: 5.5 oz (155.9 g).

Table of Contents Page No.
2.0

Demand Mode using a
DCP100A/200A Pressure

Module . . . . . . . . . . . . . . . . . . . .3

2.1

High Limit Setup . . . . . . . . . . . . . .4

2.2

Low Limit Setup . . . . . . . . . . . . . .4

2.3

High Alarm Setup . . . . . . . . . . . . .4

2.4

Low Alarm Setup . . . . . . . . . . . . .4

2.5

Auto Alarm Reset Setup . . . . . . . .4

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com