Series TID Temperature/Process Indicator

Specifications - Installation and Operating Instructions

Bulletin E-90-TID

The affordable Series TID allows user to monitor
temperature or a process value. Temperature ranges are
available from -58 to 302°F using one of our PTC or NTC
thermistors. Process values can be displayed from -999 to
999 counts using a 4 to 20 mA signal from one of our
various transmitters. The process indicator has an
adjustable span and zero on the 4 to 20 mA models.

Installation
Note: Unit must be mounted away form vibration, impacts,
water, and corrosive gases.

• Cut hole in panel 2.80 x 1.14 in (71 x 29 mm).
• Apply silicone (or rubber gasket) around the perimeter of

the hole to prevent leakage.

• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until

secure to panel.

• Remove back cover to wire unit.
• Wiring diagram is displayed on the top of the unit.

SPECIFICATIONS
Inputs:
PTC/NTC thermistor or 4 to 20 mA.
Display: 3-digits; red, green or blue display.
Range: -58 to 302°F (thermistor); -999 to 999 counts (4
to 20 mA).
Power Requirements: 110 VAC, 230 VAC, 12 VAC/DC,
24 VAC/DC.
Accuracy: Better than 1%.
Resolution: 1° or 0.01 count.
Front Panel Rating: IP64.
Agency Approvals: CE.

THERMISTOR CONNECTION DIAGRAM

LOVE CONTROLS DIVISION

Phone: 219/879-8000 www.love-controls.com

DWYER INSTRUMENTS INC.

Fax: 219/872-9057 e-mail:[email protected]

P.O. BOX 338 - MICHIGAN CITY, INDIANA 46361, U.S.A.

E-90-TID 5/25/07 3:47 PM Page 1