Dwyer SCC-POT/V User Manual

Model scc-pot/v, Single channel module, Open signal family

Advertising
background image

Model SCC-POT/V

Single Channel Module

NOTE

:

THIS

IS

A

FACTORY

CONFIGURED

UNIT

SCC

OPEN SIGNAL Family

Each SCC-POT/V unit is configured and calibrated
at the factory for the input signal range and volt-
age output range printed by the factory on the
SCC unit’s side-label.

The SCC-POT/V unit is capable of accommodat-
ing 0 to 500 Ohms or 0 to 100KOhms at its input.
The unit automatically selects the proper input
range for the connected potentiometer. Factory
configured units have been calibrated for a 0 to
10K

W

input. The unit provides a 0 to 5V or 0 to

10V output signal. Unit re-configuration requires
Dwyer Instruments, Inc. SC Configurator Utility.

This SCC unit may be reconfigured by a user at
any time via their personal computer (PC) or
handheld personal computer (HPC) by installing
Dwyer Instruments, Inc. Windows

®/

PC or Win-

dows

®/

CE HPC

SC Configurator Utility, interfac-

ing the SCC unit to the computer’s RS-232C
comm port with an SCC Configuration Cable (sold
separately), and then changing the unit’s input/
output configuration settings.

FACTORY CONFIGURATION

15 - 32VDC, 30mA external supply voltage

Mandatory:

Optional:

SCC Configuration Package (Part No. SCC-
CC-A1) Package consists of: SC
Configurator Utility and SCC Configura-
tion Cable.

REQUIREMENTS

The SCC family of single channel signal condi-
tioning and isolating modues are intelligent, user
programmable, high-accuracy, user friendly, sig-
nal conditioning units.

Each SCC model supports one (1) specific analog
signal-type on its input channel and outputs one
(1) high-level current or voltage signal depending
upon model. A diverse SCC model family per-
mits users to select the model which meets their
unique signal conditioning needs.

OPERATIONAL DESCRIPTION

INSTALLATION

1

4

3

2

6

5

GREEN LED

RED LED

CABLE

PORT

TERMINAL

BLOCK

ENCLOSURE

ENCLOSURE

COVER

SNAP-ON TAB

(COVERS COMM CABLE PORT)

SNAP-ON TAB

(TERMINAL MARKERS)

WIRING

TERMINALS

TERMINAL

SET SCREW

1 . Mount SCC unit on standard TS32 or TS35

DIN rail.

2. See wiring diagram on reverse side. Connect

external 15 to 32VDC power source to SCC
unit:
Positive (+) to SCC terminal -V OUT
Negative (-) to SCC terminal -VDC/-OUT

DIAGNOSTIC TOOLS

Two LEDs one RED and one GREEN are located
on the front face of the SCC’s enclosure and pro-
vide user with visual indication as to unit opera-
tion.

SCC models may be purchased with a factory pre-
set configuration for plug-n-play application or
available unconfigured so user may configure the
unit to meet their unique need. All SCC models
may be configured/reconfigured by a user at any-
time through use of an optional SC Configuration
Package.

Theory of Operation - An analog world input signal
arriving at the SCC unit is isolated, filtered, ampli-
fied, scaled and/or linearized (as required) by the
units onboard microprocessor under the direction
of the unit’s configuration parameters set by the
user (or factory) via Windows

®

/PC or Windows

®

/

CE HPC (Handheld Personal Computer) based SC
Configurator Utility.

The conditioned signal is then converted to a high
level analog current or voltage output signal (de-
pending upon mode) and presented at the unit’s
isolated output.

3 . Connect Potentiometer to SCC unit:

Pot 1 to SCC terminal POT 1
Pot Wiper to SCC terminal POT WPR
Pot 3 to SCC terminal POT 3

4 . Connect output actuator/device to SCC unit:

Positive (+) to SCC terminal +OUT
Negative (-) to SCC terminal -VDC/-OUT

LED FUNCTIONALITY
LED’s have three operational states:

Steady ON
Steady OFF
B l i n k i n g

Condition: GREEN = BLINKING

RED = Steady OFF

Meaning:

Module is processing data.

Condition: GREEN = Steady ON

RED = Steady ON

Meaning: 1) Configuration data is not loaded in
module memory. -OR- 2) During module re-con-
figuration both LED’s are normally ON indicat-
ing data is being properly transferred to or from
module memory.

Condition: GREEN = BLINKING

RED = BLINKING

Meaning: The measured input signal is outside
the modules configured range. When the signal is
within configured range the LED’s indicate nor-
mal operation.

All other combinations indicate the module is not