Dwyer UDL User Manual

Dwyer instruments, inc, Series udl universal input data logger

Advertising
background image

Series UDL Universal Input Data Logger

Specifications - Installation and Operating Instructions

Bulletin DA-UDL

The Series UDL Universal Input Data Loggers are available with 0, 2, or

4 universal inputs. Each universal input can be individually configured to

accept a thermocouple, RTD, thermistor, voltage, or current input. All Series

UDL data loggers have an internal temperature sensor and a digital input

which can be used as a trigger to start logging or as a pulse counter for inter-

facing with flow meters or other sensors with a pulse output. Optional fea-

tures include an internal humidity sensor, an LCD display, and an external

humidity and temperature sensor. The Series UDL loggers interface to the

USB port of a PC. The unit includes software, USB connection cable and

installed battery.

SOFTWARE FEATURES

• Graphing of downloaded data

• Zooming function

• Temperature in °F or °C

• Up to two traces per graph

• Multiple traces per graph (Full Version Only)*

• Exporting to spreadsheet (Full Version Only)*

• Viewing the data table (Full Version Only)*

• Calculating Mean Kinetic Temperature (MKT) (Full Version Only)*

• Emailing graphs (Full Version Only)*

*In order to obtain the Full Version Only features, the software upgrade key

must be purchased. To access the full version, the software key is inserted

into a USB port on the PC and the full version features are automatically

added onto the existing software.

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS

Inputs: RTD, Thermocouple, Thermistor, Current, Voltage, Slidewire.

Range: Internal temperature: -22 to 158°F (-30 to 70°C); Internal RH: 0

to 100%; External temperature: -22 to 158°F (-30 to 70°C); External RH:

0 to 100%.

Accuracy: Internal temperature: ±1°F (± 0.5°C); External temperature:

±1°F (±0.5°C) over 30 to 122°F (0 to 50°C), ±2°F (±1°C) over -30 to

32°F (-30 to 0°C) and 122 to 158°F (50 to 70°C); Internal/External RH:

±2.0%RH over 10%-90%, ±4.0%RH over 0-10% and 90-100%RH.

Memory Size: 0 or 2 universal inputs: 62,000 readings; 4 universal

inputs: 128,000 readings.

Resolution: All universal inputs: 16 Bit; Internal & external temperature:

12 Bit; Internal & external RH: 8 Bit.

Sampling Method: Stop when full or continuous logging (wrap when

full).

Sampling Rate: Selectable from 1 second to 24 hours.

Computer Requirements: Windows

®

98, Windows

®

2000, Windows

®

ME, Windows NT

®

, Windows

®

XP, and Windows Vista

®

operating system

with 16 MB RAM, one free USB port.

Power Requirements: 3.6VDC lithium AA.

Battery Life: 6 years (approx.).

Alarms: Programmable high/low.

Interface: USB port (cable included).

Housing Material: ABS plastic.

Weight: 5.8 oz (165 g).

Agency Approval: CE, RoHS.

Windows

®

, Windows NT

®

, and Windows Vista

®

are registered trademarks of Microsoft

Corporation.

3-1/16

[77.79]

4-13/16

[122.24]

2-5/8

[66.68]

4-1/4

[107.95]

1-1/4

[31.75]

DA-UDL:TEMPLATE 4/1/09 8:43 AM Page 1

Advertising