Innotech Service & Event Analyser Installation Instructions

© Mass Electronics Pty Ltd 2011

Chapter 3 – Configuring iSEA

Figure 3-7: Creating a new TCP Connection in iComm

3-2 Configure iSEA

3-2.1 Setup of Monitoring in iSEA

The steps below describe how to enable Facility Manager (FM) to monitor the Chronicle Server

service and some of its components to ensure it is running, and setup an alarm if the service fails

unexpectedly.

Notifications in FM may be set up to alert maintenance staff of various potential faults that may occur

when Chronicle is logging data, such as if the database connection fails. Database usage may also be

monitored, so that precautions may be taken when the database approaches capacity to ensure no

data is lost.

This guide assumes that the Point Reporting settings in the iSEA Configuration window are enabled,

all software detailed above has been installed and configured as specified in the relevant setup

guides, and that the user is familiar with the operation of a Microsoft Windows computer.

1. In the iComm window, right click a blank area in the top pane and add a new TCP/IP

connection.

Prior to setup, ensure that the configuration settings in iSEA are correct for your installation.

IMPORTANT

To edit the connection later, right click the connection and select Connection Properties from the context menu.