Technical Information / Datasheet

PROFINET IO Bus module

SK CU4-PNT

1.0

Erstausgabe / first issue

4913

Rck

TI 275271015

GB

version

reason for change(s)

issue

name

document

speech

Pos : 2 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ PR OFIN ET I O/ SK C U4-PN T / 275271015 / Basisinf or mationen [SK CU 4-PNT ] @ 4\ mod_1385369288406_388.doc x @ 106351 @ 555 @ 1

SK CU4-PNT

Part number: 275 271 015

PROFINET IO

®

- Internal Bus – Interface

NOTICE

Validity of this document

This document is only valid in combination with the operating instructions for the relevant frequency inverter. All
of the information that is relevant for a safe start-up of this module and the frequency inverter is only available
under these conditions.

Scope of delivery

1 x

Module

SK CU4-PNT

1 x

System bus cable set

grey / black

1 x

24 VDC cable set

brown / blue

2 x

Connecting screws

M4 x 20, cross-head

Field of use

Internal interface for the connection of a decentralised frequency inverter (SK 180E … SK 2xxE) to a
PROFINET IO field bus. This is connected to the inverter via the system bus and can directly access
up to 4 frequency inverters. 2 digital inputs are available.

Technical data

Module

Temperature range

-25°C … xx °C *

Vibration resistance

3M7

Temperature class

Class 3K3

Firmware version

V1.2 R0

Protection class

IP20

Hardware version

AA

Supply voltage

24 V ± 20

%, ≈ 100 mA

Reverse polarity protected

* The upper temperature limit depends on the frequency inverter and the operating mode

à see "Derating"

Digital input - working range

Low: 0 V … 5 V, High: 15 V … 30 V

Digital input - specific data

R

i

= 10 kΩ, input capacity: 10 nF, response time 3 ms,

inputs as per EN 61131-2 type 1