Configuration, Led indicators, Profinet io bus module – sk cu4-pnt – NORD Drivesystems TI 275271015 User Manual

Page 5: Profinet-specific led

Advertising
background image

PROFINET IO Bus module – SK CU4-PNT

TI 275271015 - 4913

5 / 8

Configuration

Configuration of the module for remote maintenance or for the system bus is carried out via the DIP
switches. The DIP - switch settings are read after a "Power On" of the module.

DIP switch

Meaning

12

11

10

9

8

7

6

5

4

3

2

1

X

X

X

No function

X

0

System bus terminating resistor not set

1

System bus terminating resistor set

Access rights for remote maintenance

0

Only read access to parameters possible.

1

Read and write access to parameters possible.

0

No control possible.

1

Control is possible.

0

TCP/IP open connection.

1

Secure TCP/IP connection.

1. System bus (DIP 1)

The system bus must be terminated at both physical
ends.

2. (DIP 2 - 9)

No function

3. Access rights for remote maintenance (DIP 10 – 12)

Via the Ethernet protocols TCP and UDP the module
and the connected frequency inverter can be
accessed using remote maintenance. The type of
access is determined via the DIP - switch with inputs
10 to 12.

Pos : 21 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /LED Anzeigen [SK CU 4-PNT] @ 4\ mod_1385046539436_388. doc x @ 106074 @ 5 @ 1

LED indicators

The operating statuses of the module are visualised using LED indicators.

No.

Name

Colour

Meaning

1

RUN

green

Ethernet State

BF

red

Ethernet Error

2

L1

green

Link 1

A1

yellow

Activity 1

3

L2

green

Link 2

A2

yellow

Activity 2

Pos : 24 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /LED Anzeigen- PROF INET spezifisc he LED [PN T Allgemein] @ 4\ mod_1385130089638_388.doc x @ 106275 @ @ 1

PROFINET-specific LED

RUN

(Ethernet State)

Meaning

BF

(Ethernet Error)

Meaning

OFF

No operating voltage
Initialisation

OFF

No error

Flashing green

No connection to PROFINET IO controller
No parameter communication
No process data communication

Flashing red

No process data communication
à e.g. wrong GSDML file

Green ON

Parameter communication active
Process data communication active

Red ON

Ethernet error

à there is no physical

connection to a further participant

Double-flashing

red

(2 x 0.25 s,+

1sec pause)

PROFINET or FI timeout,
(see also P151, P513)

1

12

ON

OF

F