PROFINET IO Bus module – SK CU4-PNT

TI 275271015 - 4913

7 / 8

Error messages

Error messages from the module - present errors or archived messages relating to the last error - can
be read out via the module parameter (P170). The error messages are lost if the module is switched
off.

Error

Meaning

Remarks

100.0

EEPROM error

EMC fault, module defective

102.0

Timeout

via P151/P513 monitoring

103.0

System bus BUS OFF

No 24V supply to the bus, connections not correct

104.0

Module temperature too high

only SK CU4-…, permissible internal temperature of the bus
module exceeded for approx. 60 sec

560.0 …
560.9

Internal error

Module not ready

561.0

General network error

561.1

Ethernet Watchdog timeout

561.2

Bus cable fault

Bus cable connection interrupted

561.3

IP address error

IP address of the module has been doubly assigned

563.0

Firmware version incompatible

The firmware version cannot be used for the device

564.0

MAC address error

Errors which occur in relation to the module are depicted as follows in the error memory of the
frequency inverter (P700 / P701).

Error
(E010)

Meaning

Remarks

10.0

Connection error

Contact to SK xU4 lost

10.1

ASIC errors

Communication to Ethernet - ASIC lost

Switch-off of the supply voltage

Reduce the temperature of the module (only SK CU4-…)

10.2

Ethernet Watchdog timeout

Telegram transfer error

Check the connections and links, program sequence and
Bus Master

10.3

Timeout by P151/P513

Telegram transfer error

Check the connections and links

Check the Watchdog time

10.4

IP address error

IP address of the module has been doubly assigned

10.5

Internal error

Module not ready for operation, configuration error

10.6

Bus cable fault

Bus cable connection interrupted

10.8

The connection between the inverter
and the module had a timeout

Only SK TU3 module

10.9

Module missing (P120)

Only SK xU4 module

Pos : 27 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ Par ameter [SK xU x-. .. Allgemei n - Fr equenzumric ht er] @ 4\ mod_1384953855694_388.doc x @ 105781 @ 5 @ 1

Parameters

Frequency inverter: The following frequency inverter parameters must be adapted for setting up
communication between the frequency inverter and the bus module (for details see frequency
converter manual).

Parameter [-Array]

Meaning

Remarks

P120 [-01]

Option monitoring

"Auto“ (default setting)

Only SK xU4

P509

Control word source

SK TU3-… on SK 5xxE: "Ethernet TU”
SK xU4-… on SK 180/SK 2xxE: "System bus"

P510 [-01 … -02]

Setpoint source

"Auto“ (default setting)

P513

Time-out

Monitoring of the SK TU3 bus module

Only SK 5xxE

P543 [-01 …-03 (-05)]
and P543 … P545

Bus actual values (1 …3 (… 5))

Possible settings according to (P418)

P546 [-01 …-03 (-05)]
and P546 … P548

Bus target values (1 …3 (… 5))

Possible settings according to (P400)

P700 [-01] / P701

Current / last failures

Information parameters

P740 / P741

Process data bus In / Out

Information parameters

P745

Module version

Information parameters

Only SK TU3

P745

Module status

Information parameters

Only SK TU3

P748

CANopen / System bus status

Information parameters