NORD Drivesystems TI 275281167 User Manual

Page 5

Advertising
background image

EtherCAT Bus module – SK TU4-ECT-C

TI 275281167 - 4913

5

EtherCAT-specific LEDs

RUN

State

Meaning

OFF

Init

No communication of process data and parameters

Flashing

Pre-Operational

Parameter communication active

No process data communication

Single Flash

Save

Operational

Parameter communication active

Limited process data communication

No restriction of actual values

Setpoints not evaluated

ON

Operational

Parameter communication active

Unrestricted process data communication

ERR

State

Meaning

OFF

No Error

EtherCAT functioning normally on the Bus Module

Flashing

Invalid

Configuration

General EtherCAT configuration error

This can be generated by an incorrect XML file.

Single Flash

Unsolicited

State Change

The module has changed the EtherCAT state without authorisation

Double Flash

Application

Watchdog

Timeout

EtherCAT or FI timeout (P513 in FI)

L/A

(Green LED)

State

Meaning

OFF

No Connection

Module not ready, no control voltage.

No bus connection (check cable connection)

Flashing

Active

Technology box connected and active

ON

Inactive

Technology box ready for operation, but no bus activity available

Pos : 21 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ LED Anz eigen- N ORD s pezifisc he LED [EI P / PO L / ECT / PNT Allgemei n] @ 3\ mod_1363773424248_388. doc x @ 61815 @ @ 1

NORD-specific LEDs

DS

(Device status)

DE

(Device error)

Meaning
Long flash

= 0.5 s on / 1 s off

Short flash

= 0.25 s on / 1 s off

OFF

OFF

Module not ready, no control voltage.

ON

OFF

Module ready, no error, at least one frequency inverter is communicating via the system bus

ON

Short flashing

Module ready, but

One or more of the connected frequency inverters has fault status

Long flashing

OFF

Module ready and at least one other participant is connected to the system bus, but

no frequency inverter connected to system bus (connection may be interrupted)

one or more system bus clients has address error

Software incompatible (module software and FI software do not match - update required)

Long flashing

Short flashing

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"

Communication on system bus disrupted

No other clients available on system bus

Module not inserted correctly or no connection to the system bus

Frequency inverter has no supply voltage

Long flashing

Short flashing

Flash interval

2 x - 1s pause

System bus is in status "Bus Off"

the system bus 24V power supply was interrupted during operation

Long flashing

Short flashing

Flash interval

3 x - 1s pause

System bus is in status "Bus Off"

No system bus 24V power supply

Long flashing

Short flashing

Flash interval

4 x - 1s pause

Module error

see parameter P170

OFF

Short flashing

Flash interval

1…7 - 1s pause

System error, internal program sequence interrupted

EMC interference (observe wiring guidelines!)

Module defective

Pos : 22 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herC at/F ehler meldung en Et herCAT Baugruppen allgemei n [ SK xU x- ECT - Allgemei n] @ 4\ mod_1384942718074_388. doc x @ 105606 @ 5 @ 1

Advertising