Module features – NORD Drivesystems TI 275900190 User Manual
Page 2

PROFINET IO Bus module – SK TU3-PNT
2 / 8
TI 275900190 - 4913
Bus specification
EtherNet/IP
Max. 100 MBaud
Cable
Min. Ethernet CAT-5
Electrical isolation 500 V
eff
Max. cable length
100 m between two
modules
Bus connection
2 x RJ45
Shield
via RJ sockets High-
bus termination
performed automatically
Resistive & capacitive to
PE
Status display
8 LEDs
PE connection
via PE post-type connector
Topology*
Star, tree, ring, linear bus
(rating less than 24 V)
Performance
Update interval for process data between module and frequency inverter
≤ 2.5 ms
Parameter read access on the frequency inverter
≈ 15 ms
Parameter write access with storage in EEPROM
≈ 25 ms
Cycle times
≥ 1 ms
Pos : 8 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ PR OFIN ET I O/M er kmal e [ PNT Allgemei n] @ 4\ mod_1385365458675_388. doc x @ 106301 @ 5 @ 1
Module features
Communication
RT (Real Time)
à Real time communication of process data
IRT (Isochronous Real Time)
à Isochronous real time communication of synchronised
process data
Addressing
Automatic address assignment via IO controller using DCP
(Discovery Configuration Protocol)
Data transfer
via Switched Ethernet
Autonegotiation
Negotiation of transfer parameters
Autocrossover
Transmission and receiver cables are automatically
crossed in the switch as necessary
Conformity classes
CC-B, and CC-C
Access for NORD diagnosis tool via
diagnosis socket on the device (if available) and possibly
via frequency inverter and
Ethernet protocols UDP or TCP/IP
Pos : 9 / Anl eit ung en/El ektr oni k/FU und St arter/ 3. / 4. Anzeige und Bedienung [ BU 0500 / BU 0200]/SK 5xxE/ 3. 2 Ü bersic ht der T echnologieboxen - 2- Mont age @ 1\ mod_1340712929975_388. doc x @ 28340 @ 5 @ 1