Module features – NORD Drivesystems TI 275900190 User Manual

Page 2

Advertising
background image

PROFINET IO Bus module – SK TU3-PNT

2 / 8

TI 275900190 - 4913

Bus specification

EtherNet/IP

Max. 100 MBaud

Cable

Min. Ethernet CAT-5

Electrical isolation 500 V

eff

Max. cable length

100 m between two
modules

Bus connection

2 x RJ45

Shield

via RJ sockets High-

bus termination

performed automatically

Resistive & capacitive to
PE

Status display

8 LEDs

PE connection

via PE post-type connector

Topology*

Star, tree, ring, linear bus

(rating less than 24 V)

Performance

Update interval for process data between module and frequency inverter

≤ 2.5 ms

Parameter read access on the frequency inverter

≈ 15 ms

Parameter write access with storage in EEPROM

≈ 25 ms

Cycle times

≥ 1 ms

Pos : 8 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ PR OFIN ET I O/M er kmal e [ PNT Allgemei n] @ 4\ mod_1385365458675_388. doc x @ 106301 @ 5 @ 1

Module features

Communication

RT (Real Time)
à Real time communication of process data

IRT (Isochronous Real Time)
à Isochronous real time communication of synchronised
process data

Addressing

Automatic address assignment via IO controller using DCP
(Discovery Configuration Protocol)

Data transfer

via Switched Ethernet

Autonegotiation

Negotiation of transfer parameters

Autocrossover

Transmission and receiver cables are automatically
crossed in the switch as necessary

Conformity classes

CC-B, and CC-C

Access for NORD diagnosis tool via

diagnosis socket on the device (if available) and possibly
via frequency inverter and
Ethernet protocols UDP or TCP/IP