PROFINET IO Bus module – SK TU3-PNT

TI 275900190 - 4913

5 / 8

PROFINET-specific LED

RUN

(Ethernet State)

Meaning

BF

(Ethernet Error)

Meaning

OFF

No operating voltage
Initialisation

OFF

No error

Flashing green

No connection to PROFINET IO controller
No parameter communication
No process data communication

Flashing red

No process data communication
à e.g. wrong GSDML file

Green ON

Parameter communication active
Process data communication active

Red ON

Ethernet error

à there is no physical

connection to a further participant

Double-flashing

red

(2 x 0.25 s,+

1sec pause)

PROFINET or FI timeout,
(see also P151, P513)

Link

(Green LED)

Activity

(Yellow LED)

Meaning

OFF

OFF

Module not ready, no control voltage.

No bus connection (check cable connection)

ON

OFF

Bus connection (cable connection) to another Ethernet device exists

No bus activity

ON

Flashing

(Blinking)

Bus connection (cable connection) to another Ethernet device exists

Bus activity present

Pos : 25 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ LED Anz eigen- N ORD s pezifisc he LED [EI P / PO L / ECT / PNT Allgemei n] @ 3\ mod_1363773424248_388. doc x @ 61815 @ @ 1

NORD-specific LEDs

DS

(Device status)

DE

(Device error)

Meaning
Long flash

= 0.5 s on / 1 s off

Short flash

= 0.25 s on / 1 s off

OFF

OFF

Module not ready, no control voltage.

ON

OFF

Module ready, no error, at least one frequency inverter is communicating via the system bus

ON

Short flashing

Module ready, but

One or more of the connected frequency inverters has fault status

Long flashing

OFF

Module ready and at least one other participant is connected to the system bus, but

no frequency inverter connected to system bus (connection may be interrupted)

one or more system bus clients has address error

Software incompatible (module software and FI software do not match - update required)

Long flashing

Short flashing

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"

Communication on system bus disrupted

No other clients available on system bus

Module not inserted correctly or no connection to the system bus

Frequency inverter has no supply voltage

Long flashing

Short flashing

Flash interval

2 x - 1s pause

System bus is in status "Bus Off"

the system bus 24V power supply was interrupted during operation

Long flashing

Short flashing

Flash interval

3 x - 1s pause

System bus is in status "Bus Off"

No system bus 24V power supply

Long flashing

Short flashing

Flash interval

4 x - 1s pause

Module error

see parameter P170

OFF

Short flashing

Flash interval

1…7 - 1s pause

System error, internal program sequence interrupted

EMC interference (observe wiring guidelines!)

Module defective

Pos : 26 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /Fehl ermeldungen Pr ofi net Baugruppen allgemein [SK xU x-PNT - Allgemein] @ 4\mod_1384961728468_388. doc x @ 105889 @ 5 @ 1