E-M-XB-V1_10

Rotronic AG
Bassersdorf, Switzerland

Document code

Unit

Instruction Manual

Document Type

XB Humidity Temperature Transmitter
User Guide

Document title

Page 14 of 27

© 2008; Rotronic AG E-M-XB-V1_10

direct current from 60 V to 400 V
(unshielded)

alternate current from 25V to 400 V
(unshielded)

in separated bundles or channels /
conduits, without minimum distance

direct and alternate current > 400 V
(unshielded)

Telephone lines

lines leading into EX-rated areas

in separated bundles or channels /
conduits, without minimum distance

Lightning protection


Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between
buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that
are suitable for underground installation.

6.2 Wiring and terminal block diagrams

6.2.1

XB2: 2-wire, loop powered transmitter


Electrical diagram


The maximum permissible cable length connecting
the XB2 to other devices is determined by the total
resistance resulting from the addition of the cable
resistance and that of the devices connected in series
with the unit. This resistance should not exceed 500
ohms.