6.4 Wiring

6.4.1

HF52: 2-wire, loop powered transmitter


Electrical diagram

The maximum permissible cable length connecting
the HF52 to other devices is determined by the total
resistance resulting from the addition of the cable
resistance and that of the devices connected in series
with the unit. This resistance should not exceed 500
ohms.






Terminal block diagram




Note: connect the + of the power supply to only one of the V+ terminals. The two terminals marked V+ are
internally connected.

Measuring humidity or temperature only

Operation of the HF52 does not require both current loops to be closed. When using the HF52 to measure
either humidity only or temperature only, close only the loop that is being used.

Using the ROTRONIC HW4 software, any unused output of the HF52 can be disabled.

Terminals

Description

K2-2: T-OUT

Temperature output (+)
OUT-2

K2-1: V+

Power supply: 10…28 VDC (+)

Terminals

Description

K1-2: H-OUT

Relative humidity or dew point (+)
OUT-1

K1-1: V+

Power supply: 10…28 VDC (+)