6.4.2

HF53: 3-wire transmitter


Electrical diagram for voltage outputs

The maximum permissible cable length can be
determined under consideration of the voltage drop
caused by the current flowing to the devices
connected to the unit. The voltage drop in the cable
depends both on cable resistance and on the
equivalent resistance of the devices connected in
parallel to the unit. The total resistance connected to
each unit output should be at least 1000 ohms. Cable
resistance should not be more than 1/1000 of the
load resistance.

Electrical diagram for current outputs


The maximum permissible cable length, connecting
the unit to other devices, is determined by the total
resistance resulting from the addition of the cable
resistance and that of the devices connected in
series with the unit. This resistance should not
exceed 500 ohms.





Terminal block diagram (analog outputs only)


Type D and W (horizontal mount)







Terminals

Description

K1-1: GND

Power supply (-) or neutral
(tied with other GND)

K1-2: V+

Power supply: 15…40 VDC (+)
or 12…28 VAC (Phase)

K1-3: -

Protective ground (see note below)

Terminals

Description

K2-4: GND

Ground (tied with other GND)

K2-3: GND

Ground (tied with other GND)

K2-2: OUT2

Temperature output (+)

K2-1: OUT1

Relative humidity or dew point (+)

V+

GND

OUT2

OUT1

GND

B2

U

B

V+

GND

B2

U

B

OUT2

OUT1

GND