E-m-hf5-v2_12 – ROTRONIC HF5 User Manual

Page 21

Advertising
background image

E-M-HF5-V2_12

Rotronic AG
Bassersdorf, Switzerland

Document code

Unit

HygroFlex HF5 Humidity Temperature
Transmitters: User Guide

Instruction Manual

Document Type

Page

21 of 36

Document title

© 2009-2013; Rotronic AG E-M-HF5-V2_12

Terminal block diagram (analog outputs and digital option)

Type D and W (horizontal mount)



















Notes:

Terminal K1-3
: this terminal (protective or earth ground) is not tied with GND. If so desired, K1-3 can be tied
with GND by closing a solder pad on the PCB (B18)

USB or TCP/IP port: this port is optional


Measuring humidity or temperature only

Operation of the HF54 does not require both current loops to be closed. When using the HF54 to measure
either humidity only or temperature only, close only the loop that is being used.

Using the ROTRONIC HW4 software, any unused output of the HF54 can be disabled.

Terminals

Description

K1-1: GND

Power supply (-) or neutral

K1-2: V+

Power supply: 15…40 VDC (+)
or 12…28 VAC (Phase)

K1-3: -

Protective ground (see note below)

Terminals

Description

K2-4: GND

Ground (tied with other GND)

K2-3: GND

Ground (tied with other GND)

K2-2: OUT2

Temperature output (+)

K2-1: OUT1

Relative humidity or dew point (+)

Terminals

Description

K3-4: D-

RS-485 Bi-directional
TX- / RX -

K3-3: D+

RS-485 Bi-directional
TX+ / RX +

K3-2: GND

Ground

K3-1: PWR

Not used