Sterlco SDA Series Medium Capacity Dehumidifying Dryer User Manual

Page 21

Advertising
background image

Cabinet Series Dehumidifying Dryer

21

E5CK Operating Parameters

The E5CK has several mode selections. Within each mode are numerous parameters that can be
set. The setting is different for the temperature control unit and the dew point display.

Before you can access the several modes of operating parameters, you must change the security
lock-out of the controller. The factory sets the security level to protect the parameters from being
accidentally changed. Below is an explanation of the operating modes, how to change out the
security level and the factory default settings.

Available E5CK Modes

Menu Display

Level 0 Mode

For normal operation. Execute AT auto-tuning, change to manual mode.

Level 1 Mode

For adjusting primary control parameters. Execute: Set alarm values; set the control period; set
PID parameters.

Level 2 Mode

For adjusting secondary control parameters. The dehumidifying dryer uses E5CK default settings.

Setup Mode

For setting the basic specifications. Set parameters for input type, scaling, output assignments and
direct/reverse operation.

Expansion Mode

For setting expanded functions. Set: ST (self-tuning), SP setting limiter. Select: advance PID or
ON/OFF control.

Option Mode

This mode is only accessible when and option board is installed.

Calibration Mode

For calibrating communication unit E53-CKF. Not used.

Manual Mode

Sets the controller to manual operation mode. Not used on dehumidifying dryers.