Sterlco SDA Series Medium Capacity Dehumidifying Dryer User Manual

Page 47

Advertising
background image

Cabinet Series Dehumidifying Dryer

47

Level 2 Cn5L input shift lower limit

-999.9 to 999.9

°C

0.0 Default

Mode Parameter

Setting

range

Default

Factory

setting

Setup

Cn-t Input Type

0 to 21

2

17

Setup

Cn-H Scaling Upper Limit

Scaling Lower Limit +1 to

9999 EU

-100

15

°F/-9C

Setup

Cn-L Scaling Lower Limit

-1999 to SP Setting Upper

Limit –0.1 EU

0

-40

°F/-40C

Setup

dP Decimal Point

0 to 3

0

Default

Setup

CnCE Parameter Initialize

Yes/No

No

Default

Setup

6Ut1 Control Output 1

Assignment

Heat/Cool/Alarm 1/Alarm 2/

Alarm 3/LBA

Heat COOL

Setup

6Ut2 Control Output 2

Assignment

Heat/Cool/Alarm 1/Alarm 2/

Alarm 3/LBA

AL-1 Default

SetUp

Sub 1 Auxiliary Output 1

Assignment

Alarm 1/Alm 2/Alm 3/LBA/S.

ERR/E333

AL-2 Default

Setup

ALt1 Alarm 1 Type

0 to 11

2

8

Setup

AL1n Alarm 1 open in alarm

NO/NC

NO

Default

Setup

ALt2 Alarm 2 Type

0 to 11

2

8

Setup

AL2n Alarm 2 open in alarm

NO/NC

NO

Default

Setup

6rEU Direct/Reverse

Operation

OR-R/OR-D OR-R

Default

Expansion SL-H Set Point Upper Limit

SP Lower Limit +1 to

Scaling Upper Limit

1300

15

°F/-9C

Expansion SL-L Set Point Lower Limit

Scaling Upper Limit to Sp

Lower Limit

-200

-40

°F/-40C

Expansion CntL PID/ON/OFF

PID/ON-OFF

PID

ON-OFF

Expansion

rESt Standby Sequence

Reset Setting Method

0/1 0

Default

Expansion

rEt Automatic Return of

Display Mode

0 to 99 SEC

0

Default

6-8 Restoring the E5CK Temperature Controller and Dew Point

Meter to Factory Setup

If preset parameters on the controller have been tampered with and it no longer properly controls
temperature and displays dew point, you can restore the controller to factory setup.