Maintenance, Trial operation – Electrolux EP19WI30LS User Manual

Page 37

Advertising
background image

35

(1) Open a hot water fixture and confirm that the Burner On lamp comes on, and that hot water is

being produced. (If necessary, repeat until the air in the gas piping is bled out).
* White smoke may be noticed from the exhaust vent during cold weather. However, this is not

a malfunction of the unit.

* If an “11” error code appears on the remote controller, turn the unit off and then back on

again, and then open a hot water fixture again.

(2) Change the temperature setting on the remote controller and check that the water temperature changes.

r If the water heater does not operate normally, refer to “Troubleshooting” in the Use and Care Manual.
* After the trial operation, clean the filter in the cold water inlet.

<If installed with a quick connect multi-system>

r5VSOUIFTZTUFNQPXFS0/XJUIUIFSFNPUFDPOUSPMMFS

r4MPXMZPQFOBIPUXBUFSàYUVSFBOEDIFDLUIBUUIFVOJUTJHOJUFTFRVFOUJBMMZ$IFDLUPTFFUIBUUIF

hot water temperature is the same as the temperature displayed on the remote controller. (*1)

* If both units do not ignite, switch which unit will ignite first by pressing the Max. or Min. Mani-fold
Pressure Set Button on the circuit board. (*2)

* If an 11 or F11 error code flashes on the remote controller, hit the Power Button on the remote

controller off and on 2 -3 times.

* If (*1) and (*2) cannot be done, the Quick Connect Cord may not be properly connected.
Check that the cord is properly connected.

14.

Maintenance

Periodically check the following to ensure proper
operation of the water heater.

r5IFWFOUJOHTZTUFNNVTUCFFYBNJOFEQFSJPEJDBMMZCZBRVBMJàFETFSWJDFUFDIOJDJBOUPDIFDLGPS

any leaks or corrosion.

r5IFCVSOFSáBNFNVTUCFDIFDLFEQFSJPEJDBMMZGPSBQSPQFSCMVFDPMPSBOEDPOTJTUFODZ

r*GUIFáBNFEPFTOPUBQQFBSOPSNBM UIFCVSOFSNBZOFFEUPCFDMFBOFE

r*GUIFCVSOFSOFFETUPCFDMFBOFE JUNVTUCFQFSGPSNFECZBRVBMJàFETFSWJDFUFDIOJDJBO

r%POPUPCTUSVDUUIFáPXPGDPNCVTUJPOBOEWFOUJMBUJPOBJS

r5IFQSFTTVSFSFMJFGWBMWFNVTUCFPQFSBUFEPODFBZFBSUPFOTVSFUIBUJUJTGVODUJPOJOHQSPQFSMZBOE

there is no obstruction. Turn the power off to the unit before opening the relief valve, and make
sure that water draining out of the valve will not cause any damage.

r*GUIFSFMJFGWBMWFEJTDIBSHFTQFSJPEJDBMMZ JUNBZCFEVFUPUIFSNBMFYQBOTJPOJOBDMPTFEXBUFS

system. Contact the water supplier or a local plumbing inspector on how to correct this situation.

Do not plug the relief valve.

r4FF6TFBOE$BSF.BOVBMGPSGVSUIFSNBJOUFOBODF

Warning: There is a scald potential if the output temperature is set too high.

Should overheating occur, or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.

Do not use this appliance if any part has been under water. Immediately call a qualified service
technician to inspect the appliance and to replace any part of the control system and any gas control
which has been under water.

Periodically check and clean the filter inside the cold water inlet of the unit.

15.

Trial Operation

The installer should test operate the unit, explain to
the customer how to use the unit, and give the owner
this manual before leaving the installation.

Unit A Ignites
Unit B Doesn't Ignite

Press Max. or Min. Manifold
Pressure Set Button on Unit B

Unit A Doesn't Ignite
Unit B Ignites

r 1SFQBSBUJPO   0QFOBIPUXBUFSàYUVSFUPDPOàSNUIBUXBUFSJTBWBJMBCMF BOEUIFODMPTF

the fixture.

(2) Open the gas supply valve.

(3) Turn on the power supply. Using the remote controller, turn on the Power

On/Off button (the Operation lamp will turn on).