Electrolux EXH09HL1WI User Manual

Page 21

Advertising
background image

ENGLISH

21

1

Valve body

2

Valve stem

3

Charge port

4

Stopper

5

Flare nut

6

Cap

Using the vacuum pump
1. Fully tighten the flare nuts at

connection point A, B, C and D.

2. Connect vacuum hose between

charging port and the manifold.

3. Connect the other charge hose

between manifold and the vacuum
pump.

4. Fully open the handle Lo of the

manifold valve.

5. Operate the vacuum pump to

evacuate.

6. Slightly loosen the flare nut of the Lo

valve on the gas pipe side.

7. Check if air is entering (noise of

the vacuum pump changes and

compound meter indicates 0 instead
of minus).

8. Tighten the flare nut.
9. Make evacuation for 15 minutes or

more and check that the compound
meter indicates -7.6 x 10

5

μmHg

(-1x10

5

Pa) (-0,7Bar).

10. Fully close the handle Lo of the

manifold valve and stop the
operation of the vacuum pump.

11. Turn the stem of the packed valve B

about 45° counterclockwise for
6~7 seconds after the gas comes
out, then tighten the flare nut again.

12. Make sure the pressure display

in the pressure indicator is a
little higher than the atmosphere
pressure. This to verify if the
refrigerant does flow correctly
through the tubes.

13. Remove the vacuum hose.
14. Replace the charging port cap.
15. Fully open the packed valve stems B

and A.

1

2

3

5

4

8

6

7