High Altitude

The manifold pressure may require adjustment to ensure

proper combustion at higher altitudes. Refer to Table 12 for

manifold pressure and pressure switch change.

Other Unit Adjustments

Primary and Secondary Limits

The primary limit is located on the heating compartment

vestibule panel. The secondary limits (if equipped) are

located in the blower compartment, attached to the back

side of the blower. These auto reset limits are factory set

and require no adjustment.

Flame Rollout Switches

This manually reset switches are located on the top of the

burner box.

Pressure Switch

The pressure switch is located in the heating compartment

adjacent to the combustion air inducer. The switch checks

for proper combustion air inducer operation before allowing

ignition trial. The switch is factory set and requires no

adjustment.

Temperature Rise

After the furnace has been started, and supply and return

air temperatures have been allowed to stabilize, check the

temperature rise. If necessary, adjust the blower speed to

maintain the temperature rise within the range shown on

the unit nameplate. Increase the blower speed to decrease

the temperature. Decrease the blower speed to increase

the temperature rise. Failure to adjust the temperature rise

may cause erratic limit operation.

Fan Control

The fan on time of 45 seconds is not adjustable. The heat

fan off delay (amount of time that the blower operates after

the heat demand has been satisfied) may be adjusted by

changing the jumper position across the five pins on the

integrated control. The unit is shipped with a factory fan off

delay setting of 90 seconds. The fan off delay affects comfort

and is adjustable to satisfy individual applications. Adjust

the fan off delay to achieve a supply air temperature between

90° and 110° F at the moment that the blower is deenergized.

Longer off delay settings provide lower return air

temperatures; shorter settings provide higher return air

temperatures. See Figure 37.

HEAT FAN OFF TIME IN SECONDS

Figure 37

Manifold Pressure Settings and Pressure Switch

Table 12

NOTE: A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
NOTE: For Altitudes of 7501' - 10,000' call Lennox Technical Support Product Applications.

For Safety, shut unit off and remove manometer as soon

as an accurate reading has been obtained. Take care

to replace pressure tap plug.