The gas furnace can be installed as shipped in either the

upflow position or the horizontal position.

Select a location that allows for the required clearances that

are listed on the unit nameplate. Also consider gas supply

connections, electrical supply, vent connection, and

installation and service clearances [24 inches (610 mm) at

unit front]. The unit must be level.

NOTE: Units with 1/2 hp blower motors are equipped with

three flexible legs and one rigid leg. See Figure 7. The rigid

leg is equipped with a shipping bolt and a flat white plastic

washer (rather than the rubber mounting grommet used with

a flexible mounting leg). The bolt and washer must be

removed before the furnace is placed into operation. After

the bolt and washer have been removed, the rigid leg will
not touch the blower housing.

Setting Equipment

WARNING

Do not install the furnace on its front or its back. Do not

connect the return air ducts to the back of the furnace.

Doing so will adversely affect the operation of the safety

control devices, which could result in personal injury or

death.

Figure 7

Units with 1/2 HP

Blower Motor.

Upflow Applications

Allow for clearances to combustible materials as indicated

on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in Figure 8.

Figure 8

Upflow Application Installation Clearances

* Front clearance In alcove Installation must be 24 in. (610 mm).

Maintain a minimum of 24 in. (610 mm) for front service access.

‡ For installation on a combustible floor, do not install the furnace

directly on carpeting, tile or other combustible materials other than

wood flooring.

† Left side requires 3 inches if a single wall vent is used on 14-1/2

inch cabinets.