Allied Air Enterprises 80G1UH User Manual

Page 7

Advertising
background image

506526-01

Page 7 of 39

Issue 1031

All gas fired appliances require air for the combustion

process. If sufficient combustion air is not available, the

furnace or other appliances will operate inefficiently and

unsafely. Enough air must be provided to meet the needs

of all fuel burning appliances and appliances such as exhaust

fans which force air out of the house. When fireplaces,

exhaust fans, or clothes dryers are used at the same time

as the furnace, much more air is necessary to ensure proper

combustion and to prevent a downdraft. Insufficient air

causes incomplete combustion which can result in carbon

monoxide.

In addition to providing combustion air, fresh outdoor air

dilutes contaminants in the indoor air. These contaminants

may include bleaches, adhesives, detergents, solvents and

other contaminants which can corrode furnace components.

The requirements for providing air for combustion and

ventilation depend largely on whether the furnace is installed

in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or

large equipment room with a volume greater than 50 cubic

feet (1.42 m

3

) per 1,000 Btu (.29 kW) per hour of the

combined input rating of all appliances installed in that space.

This space also includes adjacent rooms which are not

separated by a door. Though an area may appear to be

unconfined, it might be necessary to bring in outdoor air for

combustion if the structure does not provide enough air by

infiltration. If the furnace is located in a building of tight

construction with weather stripping and caulking around the

windows and doors, follow the procedures in the air from

outside section.

Confined Space

A confined space is an area with a volume less than 50

cubic feet (1.42 m

3

) per 1,000 Btu (.29 kW) per hour of the

combined input rating of all appliances installed in that space.

This definition includes furnace closets or small equipment

rooms.

When the furnace is installed so that supply ducts carry air

circulated by the furnace to areas outside the space

containing the furnace, the return air must be handled by

ducts which are sealed to the furnace casing and which

terminate outside the space containing the furnace. This is

especially important when the furnace is mounted on a

platform in a confined space such as a closet or small

equipment room. Even a small leak around the base of the

unit at the platform or at the return air duct connection can

cause a potentially dangerous negative pressure condition.

Air for combustion and ventilation can be brought into the
confined space either from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a

space categorized as unconfined, air can be brought in by

providing two permanent openings between the two spaces.

Each opening must have a minimum free area of 1 square

inch (645 mm

2

) per 1,000 Btu (.29 kW) per hour of total

input rating of all gas fired equipment in the confined space.

Each opening must be at least 100 square inches (64516

mm

2

). One opening shall be within 12 inches (305 mm) of

the top of the enclosure and one opening within 12 inches

(305 mm) of the bottom. See Figure 3.

Air from Outside

If air from outside is brought in for combustion and ventilation,

the confined space must have two permanent openings. One

opening shall be within 12 inches (305 mm) of the top of the

enclosure and one opening within 12 inches (305 mm) of

the bottom. These openings must communicate directly or

by ducts with the outdoors or spaces (crawl or attic) that

freely communicate with the outdoors or indirectly through

vertical ducts. Each opening shall have a minimum free

area of 1 square inch (645 mm

2

) per 4,000 Btu (1.17 kW)

per hour of total input rating of all equipment in the en-closure.

See Figures 4 and 5. When communicating with the

outdoors through horizontal ducts, each opening shall have

a minimum free area of 1 square inch (645 mm

2

) per 2,000

Btu (.56 kW) per total input rating of all equipment in the

enclosure. See Figure 6.

Figure 3

Equipment in Confined Space - All Air From Inside

NOTE: Each opening shall have a free area of at least one square

inch per 1,000 Btu (645 mm² per .29 kW) per hour of the total input

rating of all equipment in the enclosure, but not less than 100 square

inches (64546 mm²).

Advertising
This manual is related to the following products: