Scheduled shutdown screen – HP UPS Network Module User Manual

Page 39

Advertising
background image

HP UPS Network Module web interface 39

ii.

In the Switch on after the restart (individual load segments), enter the number of seconds after the

UPS restarts that the UPS Network Module should wait before restarting the load segment (from
120 to 99999 seconds, 30 seconds by default). This option allows utility power to stabilize and

disks in shared storage configurations to spin up before the server restarts.

2.

Click Save.

For more information about shutdown parameters, see "Shutdown parameters (on page

54

)."

Click Help to view online help.

Scheduled Shutdown screen

For a valid schedule, be sure the time is set correctly on the Time Settings screen (on page

34

).

While configuring scheduled shutdowns, be sure to adhere to the following rules:

The Restart Date/Time must be after the Shutdown Date/Time. If an Every Day shutdown frequency is

selected, the Restart Date/Time can be the day after the Shutdown Date/Time, but must be before the
next scheduled shutdown.

When scheduling Daily and Weekly shutdown times, verify that the Shutdown Date/Time or the Restart

Date/Time do not overlap.

To configure scheduled shutdowns:

1.

Click Scheduled Shutdowns. The List of Scheduled Shutdowns screen appears.

2.

Do one of the following:

o

Click Add Scheduled Shutdowns to add a new scheduled shutdown. The Add a New Scheduled
Shutdown screen appears.

o

In the Selected column, select a scheduled shutdown that you want to configure, and then click Edit
Scheduled Shutdown. The Edit an Existing Scheduled Shutdown Settings screen appears.

o

In the Selected column, select a scheduled shutdown that you want to remove, and then click Delete
Scheduled Shutdown.

Advertising